Johnson Controls R-410A Manual Do Utilizador

Página de 100
505430-BTG-A-0309
Johnson Controls Unitary Products
47
115°F
125°F
2250
77
99.8
8.8
69.7
60.3
50.9
-
-
-
99.1
9.6
79.9
70.5
61.0
-
-
-
72
86.5
8.7
71.4
62.0
52.6
43.1
-
-
82.7
9.5
75.2
65.7
56.3
46.8
-
-
67
73.1
8.7
73.1
63.7
54.2
44.8
35.4
-
66.4
9.5
66.4
60.9
51.5
42.0
32.6
-
62
69.9
8.5
69.9
69.9
62.0
52.6
43.2
33.7
64.9
9.4
64.9
64.9
56.8
47.3
37.9
28.4
57
69.5
8.5
69.5
69.5
60.4
50.9
41.5
32.1
64.1
9.4
64.1
64.1
55.1
45.6
36.2
26.7
2625
77
103.0
8.8
82.4
66.4
55.7
-
-
-
102.3
9.6
92.7
77.7
67.0
-
-
-
72
89.2
8.8
78.9
68.2
57.6
46.9
-
-
85.4
9.6
83.3
72.6
61.9
51.2
-
-
67
75.5
8.7
75.5
70.1
59.4
48.7
38.0
-
68.5
9.6
68.5
67.4
56.7
46.0
35.3
-
62
72.1
8.6
72.1
72.1
67.9
57.3
46.6
35.9
67.0
9.4
67.0
67.0
62.6
52.1
41.2
30.5
57
71.7
8.6
71.7
71.7
66.1
55.4
44.8
34.1
66.2
9.4
66.2
66.2
60.7
50.3
39.3
28.6
3000
77
106.2
8.9
95.1
72.5
60.5
-
-
-
105.6
9.7
105.6
84.9
73.0
-
-
-
72
92.0
8.8
86.4
74.5
62.6
50.6
-
-
88.1
9.6
88.1
79.4
67.5
55.5
-
-
67
77.8
8.7
77.8
76.5
64.6
52.6
40.7
-
70.7
9.6
70.7
70.7
62.0
50.0
38.0
-
62
74.4
8.6
74.4
74.4
73.8
61.9
50.0
38.0
69.2
9.5
69.2
69.2
68.4
56.9
44.5
32.5
57
73.9
8.6
73.9
73.9
71.9
59.9
48.0
36.1
68.3
9.5
68.3
68.3
66.4
54.9
42.4
30.5
3375
72
94.8
8.8
92.1
81.9
68.9
55.9
-
-
90.9
9.7
90.9
87.7
74.6
61.5
-
-
67
80.2
8.8
80.2
79.6
71.1
58.1
45.1
-
72.9
9.6
72.9
72.9
68.7
55.6
42.5
-
62
76.7
8.6
76.7
76.7
76.4
63.4
50.4
37.4
71.3
9.5
71.3
71.3
71.0
58.1
44.8
31.7
57
76.2
8.6
76.2
76.2
75.2
62.2
49.2
36.2
70.4
9.5
70.4
70.4
69.5
56.7
43.3
30.3
3750
72
97.7
8.8
97.7
89.3
75.2
61.1
-
-
93.7
9.7
93.7
93.7
81.8
67.6
-
-
67
82.6
8.8
82.6
82.6
77.7
63.6
49.5
-
75.2
9.6
75.2
75.2
75.2
61.2
47.0
-
62
79.0
8.7
79.0
79.0
79.0
64.9
50.8
36.7
73.5
9.5
73.5
73.5
73.5
59.3
45.2
31.0
57
78.5
8.6
78.5
78.5
78.5
64.4
50.3
36.3
72.6
9.5
72.6
72.6
72.6
58.4
44.2
30.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower 
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 
÷
 nameplate rated motor 
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
PH-07 / NH-07 Cooling Capacities  (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F)
Return Dry Bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65