PROBLEM 
POSSIBLE CAUSE 
TO CORRECT 
Check operation of unit. Replace overload if 
Overload inoperative. Opens too 
soon. 
system operation is satisfactory. 
Compressor 
attempts to 
start, or runs 
for short 
periods only. 
Compressor attempts to start 
before system pressures are 
equalized. 
Allow a minimum of 2 minutes for pressures 
to equalize before attempting to restart. 
Cycles on 
overload.  
Low or fluctuating voltage. 
Check voltage with unit operating. Check for 
other appliances on circuit. Air conditioner 
should be on separate circuit for proper 
voltage, and be fused separately. 
8.4 Troubleshooting Heating 
(Cooling/Electric Heater Models)
 
PROBLEM P
OSSIBLE CAUSE 
TO CORRECT 
Heater relay or contactor coil open.  Check continuity of coil. Inspect, test 
continuity with ohmmeter. 
Heater relay or contactor stuck 
open, pitted or burned. 
Check continuity – if open, replace. 
High limit control open. 
Check continuity. Check reason for failure. 
Open thermal fuse. 
Check voltage across heater terminals. 
Open or shorted element. 
Check amperage draw of heater. 
Fan 
Operates – 
heating 
element does 
not come on. 
Loose connections. 
Tighten all terminals. 
Restricted filter. 
Clean as recommended in Owner’s Manual. 
Cycling high limit control. 
Control is set to open at 155°F± 5°F (68.3°C 
+/- 15°C) and close at 130°F± 8°F (54.4°C +/- 
13°C). If cycling prematurely, replace control. 
Heating 
inadequate. 
 
Exhaust or fresh air door open. 
Check position of fresh air door control slide. 
Adjust cable if door does not close properly. 
Fan relay contacts open. 
Check continuity of fan relay.   
NOTE: Some models have fan relay energized 
during heating cycle while others do not. 
Inoperative system switch. 
Check connections on system switch and 
fan relay. 
Fan operates 
in "Constant" 
speed, but 
not in "Auto" 
Loose connection. 
Check connections on system switch and 
fan relay. 
Heat anticipator (resistor) 
shorted. 
Disconnect power to unit. Remove resistor 
from thermostat bulb block. Plug in unit and 
allow to operate. Feel resistor for heat. If no 
heat is felt, replace resistor. 
Long "off" 
and "on" 
cycles. 
Defective temperature sensor. 
Replace temp. sensor and check operation. 
 
 
 
Service Manual
Room Air Conditioner with R-410A
Heat Controller, Inc.