Sanyo XH3672R / C3672R Manual Do Utilizador

Página de 180
IV-7
SM831148
4. Service procedures
1
2
3
4
5
6
Judgment condition
Clear condition
F31
L02
L04
L07
L10
L13
 E07
 E06
E14
E15
E16
E20
E31
H01
Remote
controller
alarm display
Alarm
contents
Judgment and correction
Automatic recovery
EEPROM trouble
Reading/writing failure
Recovery at power 
reset
1. Check EEPROM (IC007).
2. Check outdoor unit control 
PCB.
Mismatch of indoor 
and outdoor unit types 
(Espacio, Multi )
Indoor unit judges that type 
does not match outdoor unit 
type.
Recovery at power 
reset
1. Check indoor unit EEPROM.
2. Check indoor unit control 
PCB.
Settings failure
Settings failure
Settings failure
Duplicated outdoor unit 
address (system address)
1. Check outdoor unit 
system address.
2. Check inter-unit control 
wiring.
Group control wiring is 
connected to an 
independent-control indoor 
Recovery at power 
reset
1. Check inter-unit control 
wiring.
2. Check indoor unit 
EEPROM.
Outdoor unit capacity not set.
Recovery at power 
reset
Check outdoor unit EEPROM.
Indoor-outdoor unit 
types
Outdoor unit judges that type 
does not match indoor unit 
type.
Recovery at power 
reset
1. Check indoor unit 
EEPROM.
2. Check outdoor unit control 
PCB.
Outdoor unit detected 
abnormal signal from 
indoor unit.
Serial signal receiving failure 
(including failure to verify No. 
of units)
Automatic
recovery
Automatic
recovery
1. Check inter-unit control 
wiring.
2. Check outdoor unit 
Outdoor unit sending 
failure to indoor unit
 
l
o
r
t
n
o
c
 
t
i
n
u
-
r
e
t
n
i
 
k
c
e
h
C
 
.
1
e
r
u
li
a
f
 
g
n
i
d
n
e
s
 
l
a
n
g
i
s
 
l
a
i
r
e
S
wiring.
2. Check outdoor unit control 
PCB.
Settings failure
Duplicated master unit in 
simultaneous-operation multi 
control
(Detected by outdoor unit)
Recovery at power 
reset
1. Check inter-unit control 
wiring.
2. Check indoor unit 
combination.
Automatic address 
setting failure
Automatic address 
setting failure
Automatic address 
setting failure
Indoor unit capacity too low.
Recovery at power 
reset
Recovery at power 
reset
Recovery at power 
reset
1. Check inter-unit control 
wiring.
2. Check outdoor unit control 
PCB.
 
l
o
r
t
n
o
c
 
t
i
n
u
-
r
e
t
n
i
 
k
c
e
h
C
 
.
1
.
h
g
i
h
 
o
o
t
 
y
t
i
c
a
p
a
c
 
t
i
n
u
 
r
o
o
d
n
I
wiring.
2. Check outdoor unit control 
PCB.
Outdoor unit cannot receive 
any serial signals from indoor 
units.
1. Check inter-unit control 
wiring.
2. Check outdoor unit control 
PCB.
Communications
trouble within unit
No communication possible 
with MDC for 3 minutes or 
longer.
Automatic recovery Check outdoor unit control 
PCB.
Overcurrent 
Inverter stops after alarm is 
detected.
Recovery at restart
1. Refrigerant cycle trouble, 
overload operation
2. Loose screws between HIC 
control PCB and radiating 
plate
3. Cooling failure of radiating 
plate
4. Check outdoor unit PCB 
wiring.