10.2.4 Connecting Tubing between Indoor and 
           Outdoor Units 
    •  Tightly connect the indoor side refrigerant 
      tubing extended from the wall with the outdoor  
      side tubing. (Fig. 30)
    •  To fasten the flare nuts, apply specified torque 
as table 2:
Table 2
10.2.5 Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to  
drippingof condensation, 
both tubes must be 
well insulated with proper insulation material. 
The thickness of the insulation should be a min. 
8mm. (Fig. 31, 32)
After a tube has been insulated, never try to bend  
it into a narrow curve, as this may cause to break 
or crack.
10.2.6 Taping the Tubes
    •  At this time, the 2 refrigerant tubes (and 
      electrical wire if codes permit) should be taped
      together with armoring tape. The drain hose 
      may also be taped together as 1 bundle with 
      the tubing.
    •  Wrap the armoring tape from the bottom of the 
      outdoor to the top of tubing where it enters the
      wall. As you wrap the tubing, overlap half of 
      each previous tape turn. (Fig. 33)
    •  Clamp tubing bundle to wall, using 1 clamp 
      approx. every 120cm.
Do not wind the armoring tape too 
tightly, since this will decrease the
heat insulation effect. Also, be sure 
the condensation drain hose splits 
away from the bundle and drips 
clear of the unit and the tubing.
10.2.7 Finish the Installation
    After finishing insulating and taping over the 
    tubing, use sealing putty to seal off the hole in 
    the wall to prevent rain and draft from entering. 
    (Fig. 34) shows refrigerant tubing taped 
    separately from the drain hose.
Indoor unit
Outdoor unit
Spanner
Torque wrench
Fig.30
Insulation
Fig.31
Insulation
Min.
8 mm
Thickness:
min. 8 mm
Fig.32
Fig.33
Clamp
Insulated tubes
Apply putty here
Tubing
Fig.34
Tube Dia.
Tightening Torque
Approx. 15 - 20 N.m (1.5 - 2.0 kg.m)
9.52 mm
6.35 mm
12.7 mm
Approx. 35 - 40 N.m (3.5 - 4.0 kg.m)
Approx. 50 - 55 N.m (5.0 - 5.5 kg.m)
CAUTION
IMPORTANT
NOTE
10. INSTALL OUTDOOR UNIT
Installation Service
15.88 mm
Approx. 68 - 82 N.m (6.8 - 8.2 kg.m)