NOTE
Air and moisture remaining in the refrigerant 
system have undersirable effects as indicated 
below. Therefore, they must be purged 
completely.
•  Pressure in the system rises
•  Operating current rises
•  Cooling (or heating) efficiency drops
•  Moisture in the air may freeze and block 
   capillary tubing.
•  Water may lead to corrosion of parts in the 
   refrigerant system.
Hi
Lo
Indoor unit
Outdoor unit
Manifold valve
Pressure
gauge
Vacuum pump
Fig.35
AIR PURGING WITH A VACUUM PUMP
(FOR TEST RUN)
1. Check that each tube (both narrow and wide 
    tubes) between the indoor and outdoor units 
    have been properly connected and all wiring 
    for the test run has been completed. Noted 
    that both narrow and wide tube service valves
    on the outdoor unit are kept closed at this 
    stage.
 
2. Using a adjustable wrench or box wrench, 
    remove the valve caps from the service on
     both narrow and wide tubes.
3. Connect a vacuum pump and a manifold 
    valve (with pressure gauges) to the service 
    port on the wide tube service valve. (Fig.35)
Be sure to use a manifold valve for air 
purging. If it is not available, use a stop valve 
for this pupose. The "Hi" knob of the 
manifold valve must always be kept closed. 
4. With the "Lo" knob of the manifold valve open, 
    run the vacuum pump. The operation time for 
    the vacuum pump varies with tubing length 
    and the capacity of the pump. The following
    table shows the amount of time for evacuation:
Table 3
       Required time for evacuation when
capacity of 100 liter/h vacuum pump is used 
If tubing length is
   less than 7 m  
10 min. or more
 15 min.or more
If tubing length is
   more than 7 m  
The require time in the table
3 is calculated based on the 
assumption that the ideal 
(or target) vacuum condition 
is around 10 mmHg abs. 
10.3 Air Purging
CAUTION