Control/conditions
HEAT
When defrost operation 
begins, frost has formed 
on the outdoor unit 
(when the ambient air 
temperature is low).
Defrost operation begins based on outdoor heat 
exchanger temperature and outdoor air 
temperature conditions.
Non-stop defrost (Refer to Fig. 1)
1. After HEAT operation begins, the temperature 
of the outdoor heat exchanger is at or below the 
L1 line for 35 minutes.
(If outdoor air temperature is less than –3 °C,
the time is 48 minutes) 
2. After HEAT operation begins, the temperature 
of the outdoor heat exchanger is at or below the 
L2 line for 120 minutes.
The 4-way valve remains ON during defrost.
Non-stop defrost
Unit operation
Explanation
The outdoor fan stops and the solenoid 
valve turns ON, allowing the refrigerant to
bypass the indoor unit.
Indoor fan : Stopped
Outdoor fan : Stopped
Compressor : 80 Hz
Solenoid valve (for hot gas bypass): ON
4-way valve : Remains ON
Operation lamp : Red and orange ON 
                            alternately
Defrost release
Indoor fan turns ON.
After 10 seconds, the solenoid valve 
(for hot gas bypass) turns OFF.
When the cold air feel has disappeared, 
the indoor fan starts and gradually increases 
speed until it reaches the set speed.
STOP
[Clean defrost]
Defrost is performed 
when the outdoor unit is 
stopped, and the 
temperature of the 
outdoor unit coil is at or 
below the L1 line. 
(Refer to Fig. 1.)
All indicator lamps turn OFF. The indoor and 
outdoor units stop.
The operating frequency during defrost is 
80 Hz. (Frequency is lowered if the current 
peak cut-off function is activated.)
The maximum length of a single defrost 
operation is 12 minutes.
For the outdoor heat exchanger temperature 
conditions for ending defrost, refer to Table 1.
Operation is restarted 
within 4 hours (only when 
AUTO mode is selected 
with the remote 
controller).
Within 4 hours after operation was stopped, it is 
assumed that there has been no significant 
change in the indoor and outdoor temperatures, 
and the previous conditions (HEAT) are stored.
Table 1
Starts operating in the same operating mode 
(HEAT) and with the same temperature 
settings as before operation was stopped.
Operation starts after 4 
hours or more have 
passed.
Outdoor heat
exchanger temperature
Fig. 1
Outdoor air
temperature
(–20)
0
(– 6)
(– 7)
(– 24)
(– 25)
L2
L1
New operation begins based on the 
temperature conditions at the time the 
ON/OFF button is pressed.
Temperature of releasing
*1 The temperature for releasing of defrosting is (20 °C) or higher when the 
outdoor air temperature is less than 0 °C.
Defrost operation time
Heat exchanger 
temperature for 
releasing defrosting
Less than 2 minutes
2 minutes or more
No releasing
14 °C or higher (*1)