MODE CONTROL
The mode control pad(s) allow the selection of the operating 
modes of the unit.
There is a two second delay before the mode activates its 
appropriate relay.
OPERATING SEQUENCE / CHARACTERISTICS 
AND FEATURES
Compressor Operation
The  run  state  of  the  compressor  is  determined  by  the 
difference  between  the  indoor  ambient  temperature  and 
the  set  temperature.  See  specifi c  mode  of  operation  for 
details.
Compressor Time Delay: 180 seconds
This  feature  is  initiated  every  time  the  compressor  is  de-
energized, either due to:
(1) satisfying the temperature set point
(2) changing mode to fan only
(3) a power interruption or
(4) turning the unit off
The compressor is also time delayed for 3 minutes when the 
control is fi rst plugged in or power is restored after failure.
When the compressor cycles off as a result of satisfying the 
“load”,  the  time  delay  is  typically  timed  out  during  the  off 
cycle. Compressor time delay is bypassed by “Test Mode”.
Return Air Temperature Sensor
The control range is 60°F to 90°F +/- 2.0°F.
Frost Protection Sensor
Temperature settings:
Disable  the  compressor  when  sensing  30°  +/-  3°F  for  2 
minutes continuously.
Enable compressor @ 55° +/- 5°F.
The fan should not be affected by the Frost Protection. It 
should continue to function normally if freeze protection is 
called for.
COOL MODE FOR XQ MODELS
When  in  the  COOL  mode,  the  control  will  turn  on  the 
compressor when the indoor temperature is 1.5°F above the 
set point and turn off the compressor when the ambient gets 
below the set point by 1.5°F. The fan will run continuously.
MONEY SAVER MODE
When in MONEY SAVER mode, the system will be turned 
on when the indoor temperature gets above the set point by 
0.75°F and turns off when the indoor temperature gets below 
the set point by 0.75°F. The fan will turn on 5 seconds before 
the compressor and turn off 5 seconds after the compressor 
stops. If the compressor is delayed the fan will continue to 
run while the compressor restarts. If the thermostat remains 
satisfi ed for more than approximately 9 minutes, the fan will 
turn on for a period of 90 seconds for air sampling. Operation 
in MONEY SAVER mode will light both the MONEY SAVER 
and COOL indicators.
ELECTRONIC CONTROL SEQUENCE OF OPERATION
11
FAN ONLY MODE
When  in  the  FAN  ONLY  mode,  the  compressor  will  not 
operate. The fan will run continuously at the user-selected 
speed  (see  “Fan  Speed  Set”  below).  Smart  Fan  is  not 
available in FAN ONLY Mode.
FAN SPEED SET
XQ fan speed is changed by pressing FAN SPEED button 
and scrolling through F1, F2, F3 and SF (Smart Fan) in the 
digital display.
There will be a 2 second delay before the fan speed changes 
to prevent unnecessary switching of the relays during fan 
speed selection.
SMART FAN
On  the  XQ  model,  smart  fan  is  activated  by  pressing  the 
FAN  SPEED  button  and  scrolling  through  speeds  until 
“SF”  appears  in  the  digital  display.  Using  the  remote 
control,  Smart  Fan  is  selected  by  the  fourth  push  of  Fan 
Speed button.
Smart fan changes fan speeds based on the temperature 
differential between the ambient and set temperatures.
CHECKING ROOM TEMPERATURE
Check the room temperature at the electronic control  
pad by pressing the “FAN SPEED” button and the 
TEMP     ” button at the same time on XQ models.
The indoor temperature will display for 10 seconds. Indoor  
temperature  can  be  viewed  in  all  modes,  including  the 
TEST  mode.  The  display  can  be  changed  back  to  SET 
temperature  by  pressing  any  key,  except  the  ON/OFF 
button, or after 10 seconds has elapsed.
KEEP ALIVE
The electronic control has a memory to retain all functions 
and status as set up by the user in the event of a power 
failure. Once power is restored to the unit there is a two 
second delay before the fan comes on and approximately 
three  minutes  delay  before  the  compressor  is  activated, 
providing  that  the  mode  was  set  for  cooling  and  the  set 
point temperature has not been met in the room.
REBOOT/RESET THE CONTROL BOARD
With unit on, press “MODE” and “TEMP/HOUR      ” buttons 
simultaneously for 10 seconds. If the panel will reboot, you 
will  hear  the  fan  come  on  and  the  temperature  window 
will  read  60°F.  If  this  happens,  turn  the  unit  off  for  about 
10  seconds  and  then  turn  it  back  on  to  fi nish  the  reboot 
cycle. If the panel does not reboot, you possibly need to 
replace it.