REmotE tHERmoStat anD Low VoLtagE ContRoL 
CONNeCTIONS (Continued)
Desk Control Terminals
The Friedrich VERT-I-PAK has built-in provisions for 
connection to an external switch to control power to the unit. 
The switch can be a central desk control system or even a 
normally open door switch.
For desk control operation, connect one side of the switch to 
the D1 terminal and the other to the D2 terminal (See figure 9).
Whenever the switch closes, the unit operation will stop.
Maximum Wire Length for Desk Control Switch
  Wire Size 
Maximum Length
 
#24 
400 ft.
 
#22 
600 ft.
 
#20 
900 ft.
 
#18 
1500 ft.
 
#16 
2000 ft.
Auxiliary Fan Control
The Smart Center also has the ability to control a 24VAC 
relay to activate an auxiliary, or transfer, fan. The outputs 
are listed as F1 and F2 on the control board.
To connect the relay, simply wire one side of the relay to 
F1 and the other side to F2. Anytime that the fan runs, the 
terminals will send a 24VAC signal to the relay. The relay 
must be 24 VAC, 50mA or less.
Note: The relay and auxiliary fans must be field supplied.
Note: The desk
control system and 
switches must be 
field supplied.
Thermostat Connections
Thermostat Configuration
  C  =  Common Ground
  W  =  Call for Heating
  Y  =  Call for Cooling
  R  =  24V Power from Unit
 GL  =  Call for Fan (Low Speed)
 GH  =  Call for Fan (High Speed)
  B  =  Reversing Valve Energized in heating mode
*If only one G terminal is present on thermostat, connect 
to GL for low fan or to GH for high fan operation.
NOTE: It is the installer’s responsibility to ensure that all 
control wiring connections are made in accordance with 
the Freidrich installation instructions.  Improper connec-
tion of the thermostat control wiring and/or tampering with 
the unit’s internal wiring can void the equipment warranty. 
Questions concerning proper connections to the unit 
should be directed to the factory: 210-357-4400.
An improperly configured t-stat can be the 
cause of improper operation. Ensure to 
correctly configure the t-stat (see owner’s 
manual).