Friedrich 000 BTU'S Manual Do Utilizador

Página de 56
14
Low fan
High fan
Fan only
Power
Temp
Temp
Cool
Heat
 
1  2  3  4  5  6  7  8
O
N
Electronic Control Configuration
The adjustable control dip switches are located at the lower 
left hand portion of the digital Smart Center. The inputs are 
only visible and accessible with the front cover removed from 
the Unit.
Factory Dip Switch Configuration
Dip Switch Setting
Switches 1-4  ON
Switch 5-7 OFF
Switch 8 ON
Room Freeze Protection – Switch 6
Units are shipped from the factory with the room freeze protec-
tion disabled. Room Freeze Protection can be switched on at 
the owner’s preference by moving Dip Switch 6 to ‘ON’. This 
feature will monitor the indoor room conditions and in the event 
that the room falls below 40°F the unit will cycle on high fan with 
the electric heater. This occurs regardless of mode.
Emergency Heat Override – Switch 7
Units are shipped from the factory with the room emergency 
heat override disabled. In the unlikely event of a compressor 
failure a heat pump unit may be switched to operate in only the 
electric heat mode until repairs can be made, by moving Dip 
Switch 7 to ‘ON’.
Discharge Air Sensor Override – Switch 8
This switch MUST remain in the “ON” position for Vert-I-Pak  
models, since they do not use a discharge air sensor.  If the  
switch is positioned in the “OFF” position on these models it 
will result in the erroneous display Error Code 14 indicating that 
the Discharge air temperature sensor is open or shorted.
Note: In order for the control to recognize “Dip” switch 
setting  changes,  the  unit  must  be  disconnected 
from power supply when making any configuration 
changes.
Error Code Diagnostics
The VPAK electronic control continuously monitors the Vert-I-Pak 
unit operation and will store error codes if certain conditions 
are witnessed. In some cases the unit may take action and shut 
the unit off until conditions are corrected.
To access the error code menu press the ‘
HEAT’ and ‘HIGH
FAN’ buttons simultaneously for three seconds. If error codes 
are present they will be displayed. If multiple codes exist you 
can toggle between error codes using the
 temp up ▲ button. To 
clear all codes press the 
temp down ▼ button for three seconds 
while in the error code mode. To exit without losing codes 
press the ‘Low Fan’ button.
Button Location for Vert-I-Pak Models
With the remote thermostat escutcheon installed, the button 
locations to access the diagnostics mode can be located as 
shown below.
Electronic Control Error Code 
Diagnostics and Test Mode
* Heat and high fan - access error codes
*  Temp up ▲ and temp down ▼ - toggle between error codes
*  Low fan - exit error code mode without losing stored error
   codes.
*  Temp down ▼ - clears all error codes
NOTE: Hold buttons down for three seconds.