Reversing valve: 
Always 
de-energized when “Cool” switch is selected on thermostat.
Compressor operation:    
If ambient indoor temperature is above set point temperature depending on t-stat differential and 
the compressor is not time delayed, turn on compressor.  If ambient indoor temperature is
below set point depending on t-stat differential, turn off the compressor. 
 
Compressor time delay:  
The 
time delay feature is de-energized for a period of time that varies randomly from 180 to 
240 seconds. Compressor time delay is initiated every time the compressor is 
“off” due to:  
(1) Satisfying the temperature set point,   
(2) Changing mode to fan only    
(3 )Turning the unit off.    
(4) Control is first energized or when power is restored after failure  
Note: Time delay is disabled during Test Mode.  
Indoor coil frost protection (Error Code 07):  
While in cool mode: If the indoor coil frost protection sensor reads 
30°F for 2 minutes continu-
ously, 
turn off the compressor, but continue fan operation. While the compressor is out and the 
fan is running: when the indoor coil frost protection sensor reaches 
45°Fturn on the compres-
sor. However, the compressor must still wait a standard time of 
180 to 240 seconds. While 07 
flash, heat  operation is disabled.  
Fan delay:   
This is only for 
fan ‘cycle’ mode and not for fan ‘continuous’ mode.  When unit  cycles cool-
ing ON – start the fan 5 seconds EARLY. When unit cycles cooling OFF –  DELAY the fan off 
for 30 seconds.  Note: the fan delay is disabled during 
Test Mode.  
Reversing valve:  Always de-energized when “Heat” button is pushed. 
 
Compressor operation: Compressor does not operate in this mode.
Electric heat operation:  If temp is below set point, depending on t-stat differential, turn on 
electric heat. If Ambient is above set point depending on t-stat differential, turn off the electric 
heat.  
Fan delay:  This is only for fan ‘cycle’ mode and not for fan ‘continuous’ mode.  When unit  
cycles heating 
ON – start the fan 5 seconds EARLY. When unit cycles heating OFF – DELAY 
the fan off for 
15 seconds. Note: the fan delay is disabled during Test Mode.     
VPak ELECtRonIC ContRoL BoaRD anD waLL 
tHERmoStat SEqUEnCE oF oPERatIon (Continued)
CooL moDE ContRoL FEatURES FoR CooL wItH ELECtRIC HEat UnItS
ELECtRIC HEat moDE ContRoL FEatURES FoR CooL wItH ELECtRIC 
HEat UnItS