Reversing valve: 
Always 
energized when “Heat” is selected on thermostat.
Compressor operation depends on t-stat settings:    
If ambient indoor temperature is below the set point temperature depending on t-stat differential 
and the compressor is not time delayed, turn on compressor.  If ambient indoor temperature is
below set point depending on t-stat differential, turn off the compressor. 
 
Compressor Time Delay:  
The time delay feature is de-energized for a period of time that varies 
randomly from 180 to 240 
seconds. Compressor time delay is initiated every time the compressor is “off” due to:  
(1) Satisfying the temperature set point,   
(2) Changing mode to fan only    
(3 )Turning the unit off.    
(4) When control is first energized or when power is restored after failure  
Note: Time delay is disabled during 
Test Mode.  
Heat:  
When there is a call for heat from the Wall thermostat the 
PCB will receive signals on terminal 
WBGL or GHDuring compressor time delay, electric heat will turn on first. When com-
pressor time delay is 
UP, the compressor will turn on.  
Condition:  
If outdoor coil temperature sensor 
drops to 30°F for less than 2 consecutive minutes, then unit 
will switch to electric heat. Thereafter, unit will switch back to Heat Pump heat if outdoor coil 
temperature sensor rises to 
45°F or greater.  
Fan delay:   
This is only for 
fan ‘cycle’ mode and not for fan ‘continuous’ mode.  When unit  cycles cool-
ing ON – start the fan 5 seconds EARLY. When unit cycles cooling OFF –  DELAY the fan off 
for 30 seconds.  Note: the fan delay is disabled during 
Test Mode.  
Emergency Heat:  
When compressor fails in heating season, allows user to disable Heat Pump. Heating with elec-
tric heat only (See DIP switch position 7). 
VPak ELECtRonIC ContRoL BoaRD anD waLL 
tHERmoStat SEqUEnCE oF oPERatIon (Continued)
HEat PUmP moDE ContRoL FEatURES FoR HEat PUmP wItH ELECtRIC 
HEat UnItS