EXAMPLE: Airfl ow requirements are calculated as follows: 
(Having a wet coil creates additional resistance to airfl ow. 
This addit ional resistance must be taken into consideration 
to obtain accurate airfl ow information.
1 ½ TON SYSTEM ( 18,000 Btu) 
Operating on high speed @ 230 volts with dry coil
measured external static pressure .20
Air Flow = 500 CFM
In the same SYSTEM used in the previous example but 
having  a  WET  coil  you  must  use  a  correction  factor  of 
.94 (i.e. 500 x .94=470 CFM) to allow for the resistance 
(internal) of the condensate on the coil.
It is important to use the proper procedure to check external 
Static  Pressure  and  determine  actual  airfl ow.  Since  in 
the case of the VERT-I-PAK, the condensate will cause 
a reduction in measured External Static Pressure for the 
given airfl ow.
It is also important to remember that when dealing with 
VERT-l-PAK  units  that  the  measured  External  Static 
Pressure increases as the resistance is added externally 
to the cabinet.  Example:  duct work, fi lters, grilles.
 
 
External Static Pressure
External Static Pressure can best be defi ned as the pressure 
difference (drop) between the Positive Pressure (discharge) 
and  the  Negative  Pressure  (intake)  sides  of  the  blower.  
External Static Pressure is developed by the blower as a 
result of resistance to airfl ow (Friction) in the air distribution 
system EXTERNAL to the VERT-I-PAK cabinet.
Resistance applied externally to the VERT-I-PAK (i.e. duct 
work, coils, fi lters, etc.) on either the supply or return side 
of  the  system  causes  an  INCREASE  in  External  Static 
Pressure accompanied by a REDUCTION in airfl ow.
External Static Pressure is affected by two (2) factors.
1.  Resistance to Airfl ow as already explained.
2.  Blower Speed. Changing to a higher or lower blower 
speed will raise or lower the External Static Pressure  
accordingly.
These affects must be understood and taken into consideration 
when checking External Static Pressure/Airfl ow to insure that 
the system is operating within design conditions.
Operating a system with insuffi cient or excessive airfl ow 
can  cause  a  variety  of  different  operating  problems. 
Among these are reduced capacity, freezing evaporator 
coils, premature compressor and/or heating component 
failures. etc.
System airfl ow should always be verifi ed upon completion 
of a new installation, or before a change-out, compressor 
replacement, or in the case of heat strip failure to insure 
that the failure was not caused by improper airfl ow.
Checking External Static Pressure
The  airflow  through  the  unit  can  be  determined  by 
measuring the external static pressure of the system, and 
consulting the blower performance data for the specifi c 
VERT-I-PAK.
  1.  Set up to measure external static pressure at the 
supply and return air.
  2.  Ensure the coil and fi lter are clean, and that all the 
registers are open.
  3.  Determine  the  external  static  pressure  with  the 
blower operating.
  4.  Refer  to  the  Air  Flow  Data  for  your  VERT-I-PAK 
system to fi nd the actual airfl ow for factory-selected 
fan speeds.
  5.  If the actual airfl ow is either too high or too low, the 
blower speed will need to be changed to appropriate 
setting or the ductwork will need to be reassessed 
and corrections made as required. 
  6.  Select  a  speed,  which  most  closely  provides  the 
required airfl ow for the system.
  7.  Recheck  the  external  static  pressure  with  the 
new  speed.  External  static  pressure  (and  actual 
airfl ow) will have changed to a higher or lower value 
depending upon speed selected. Recheck the actual 
airfl ow  (at  this  "new"  static  pressure)  to  confi rm 
speed selection.
  8.   Repeat  steps  8  and  9  (if  necessary)  until  proper 
airfl ow has been obtained.
Checking Approximate Airfl ow
If  an  inclined  manometer  or  Magnehelic  gauge  is  not 
available  to  check  the  External  Static  Pressure,  or  the 
blower  performance  data  is  unavailable  for  your  unit, 
approximate air fl ow call be calculated by measuring the 
temperature rise, then using tile following criteria.
KILOWATTS x 3413
=  CFM
Temp Rise x 1.08
Electric Heat Strips
The  approximate  CFM  actually  being  delivered  can  be 
calculated by using the following formula:
DO NOT simply use the Kilowatt Rating of the heater (i.e. 
2.5, 3.4, 5.0) as this will result in a less-than-correct airfl ow 
calculation.  Kilowatts may be calculated by multiplying 
the  measured  voltage  to  the  unit  (heater)  times  the 
measured current draw of all heaters (ONLY) in operation
 to obtain watts. Kilowatts are than obtained by dividing 
by 1000.