NOTE:  System  operating  pressures  must  be  near 
normal before valve can shift
REVERSIng VaLVE DESCRIPtIon/oPERatIon  
The Reversing Valve controls the direction of refrigerant flow 
to the indoor and outdoor coils. It consists of a pressure-
operated, main valve and a pilot valve actuated by a solenoid 
plunger. The solenoid is energized during the heating cycle 
only. The reversing valves used in the VPAK system is a 
2-position, 4-way valve.
The single tube on one side of the main valve body is the  
high-pressure inlet to the valve from the compressor. The  
center  tube  on  the  opposite  side  is  connected  to  the  low  
pressure  (suction)  side  of  the  system.  The  other  two  are  
connected to the indoor and outdoor coils. Small capillary 
tubes connect each end of the main valve cylinder to the   
“A” and “B” ports of the pilot valve. A third capillary is a common 
return line from these ports to the suction tube on the main 
valve body. Four-way reversing valves also have a capillary 
tube from the compressor discharge tube to the pilot valve.   
 
The piston assembly in the main valve can only be shifted  
by the pressure differential between the high and low sides  
of  the  system.  The  pilot  section  of  the  valve  opens  and 
closes ports for the small capillary tubes to the main valve  
to cause it to shift. 
ELECTRIC SHOCK HAZARD 
WARNING
Disconnect  power  to  the  unit  before  servicing. 
Failure  to  follow  this  warning  could  result  in 
serious injury or death.