Friedrich 000 BTU'S Manual Do Utilizador

Página de 56
32
Reversing Valve in Heating Mode  
tEStIng tHE CoIL 
 
The solenoid coil is an electromagnetic type coil mounted 
on the reversing valve and is energized during the 
operation of the compressor in the heating cycle.
1.   Turn off high voltage electrical power to unit. 
2.   Unplug line voltage lead from reversing valve coil. 
3.   Check for electrical continuity through the coil. If you 
do not have continuity replace the coil. 
4.   Check from each lead of coil to the copper liquid line 
as it leaves the unit or the ground lug. There should 
be no continuity between either of the coil leads 
and ground; if there is, coil is grounded and must be 
replaced. 
5.   If coil tests okay, reconnect the electrical leads. 
6.   Make sure coil has been assembled correctly. 
NOTE: Do not start unit with solenoid coil removed from 
valve, or do not remove coil after unit is in operation. This 
will cause the coil to burn out.
CHECkIng tHE REVERSIng VaLVE
 
NOTE: You must have normal operating pressures before  
the reversing valve can shift.
Check  the  operation  of  the  valve  by  starting  the  system 
and  switching  the  operation  from  “Cooling”  to  “Heating” 
and then back to “Cooling”. Do not hammer on valve.
Occasionally, the reversing valve may stick in the heating 
or cooling position or in the mid-position.
When  sluggish  or  stuck  in  the  mid-position,  part  of  the 
discharge gas from the compressor is directed back to the 
suction side, resulting in excessively high suction pressure. 
 
Should the valve fail to shift from coooling to heating, block 
the air flow through the outdoor coil and allow the discharge 
Reversing Valve in Cooling Mode  
ELECTRIC SHOCK HAZARD 
WARNING
Unplug  and/or  disconnect  all  electrical  power 
to  the  unit  before  performing  inspections, 
maintenances or service. 
Failure to do so could result in electric shock, 
serious injury or death.
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure  to  follow  these  procedures  could 
result in serious injury or death. 
WARNING
HIGH PRESSURE HAZARD 
pressure to build in the system. Then switch the system 
from heating to cooling.
If the valve is stuck in the heating position, block the air 
flow through the indoor coil and allow discharge pressure 
to  build  in  the  system.  Then  switch  the  system  from 
heating to cooling.
Should  the  valve  fail  to  shift  in  either  position  after 
increasing the discharge pressure, replace the valve.
Dented  or  damaged  valve  body  or  capillary  tubes  can 
prevent the main slide in the valve body from shifting.
If you determing this is the problem, replace the reversing 
valve.
After  all  of  the  previous  inspections  and  checks  have 
been  made  and  determined  correct,  then  perform  the 
“Touch Test” on the reversing valve.