Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211.
Method  A.  12”  (304.8  mm)  Clearance  to  Combustible  Wall  Member: 
Using a minimum thickness 3.5” (89 mm) brick and a 5⁄8” (15.9 mm) 
minimum wall thickness clay liner, construct a wall pass-through.  The 
clay liner must conform to ASTM C315 (Standard Specification for Clay 
Fire Linings) or its equivalent. Keep a minimum of 12” (305 mm) of brick 
masonry between the clay liner and wall combustibles.  The clay liner 
shall run from the brick masonry outer surface to the inner surface of the 
chimney flue liner but not past the inner surface.  Firmly grout or cement 
the clay liner in place to the chimney flue liner.  
Method B. 9” (229 mm) Clearance to Combustible Wall Member: Using 
a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney section 
with insulation of 1” (25.4 mm) or more, build a wall pass-through with a 
minimum 9” (229 mm) air space between the outer wall of the chimney 
length  and  wall  combustibles.  Use  sheet  metal  supports,  fastened 
securely to wall surfaces on all sides, to maintain the 9” (229 mm) air 
space.  When fastening supports to chimney length, do not penetrate 
the chimney liner (the inside wall of the Solid-Pak chimney). The inner 
end of the Solid-Pak chimney section shall be flush with the inside of the 
masonry  chimney  flue  and  sealed  with  a  non-water  soluble refractory 
cement. Use this cement to also seal to the brick masonry penetration.
Method  C.  6”  (152.4  mm)  Clearance  to  Combustible  Wall  Member: 
Starting  with  a  minimum  24  gauge  (.024”  [0.6  mm])  6”  (152.4  mm) 
metal  chimney  connector  and  a  minimum  24  gauge  ventilated  wall 
thimble which has two air channels of 1” (25.4 mm) each, construct a 
wall pass-through. There shall be a minimum 6” (152.4 mm) separation 
area containing fiberglass insulation, from the outer surface of the wall 
thimble  to  wall  combustibles.  Support  the  wall  thimble  and  cover  its 
opening with a 24 gauge minimum sheet metal support. Maintain the 
6” (152.4 mm) space. There should also be a support sized to fit and 
hold the metal chimney connector. See that the supports are fastened 
securely to wall surfaces on all sides. Make sure fasteners used to secure 
the metal chimney connector do not penetrate chimney flue liner.  
Method D.  2” (50.8 mm) Clearance to Combustible Wall Member: Start 
with a solid-pak listed factory-built chimney section at least 12” (304 mm) 
long, with insulation of 1” (25.4 mm) or more, and an inside diameter of 
8” (2” [51 mm] larger than the 6” [152.4 mm] chimney connector). Use 
this as a pass-through for a minimum 24 gauge single-wall steel chimney 
connector. Keep solid-pak section concentric with and spaced 1” (25.4 
mm) off the chimney connector by way of sheet metal support plates 
at both ends of chimney section.  Cover opening, and support chimney 
section on both sides, with 24 gauge minimum sheet metal supports. 
See that the supports are fastened securely to wall surfaces on all sides.
 
Make sure fasteners are used to secure chimney flue liner.
NOTES:
1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through 
system and the chimney wall, to but not past the inner flue liner face.
2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.
Figure 18: Chimney Through Wall - Method A.
Figure 19: Chimney Through Wall - Method B.
Figure 21: Chimney Through Wall - Method D.
Figure 20: Chimney Through Wall - Method C.