Enviro 1200 Freestanding Manual Do Utilizador

Página de 45
27
At least
3 feet (914 mm)
Hearthpad
Floor
Pedestal
Woodstove
Optional
fan
Outside air connection
through wall or floor
Double wall pipe
Ceiling support
Ceiling
Spark arrestor cap
Roof flashing
Roof
Radiation Shield
Insulated
chimney
Bolt stove to floor
Figure 28: Freestanding installation into mobile home.
The pedestal must be firmly bolted to the floor using two (2) 1⁄4” bolts. Be sure to replace any insulation 
or panels removed when fastening the bottom nuts.
If room air starvation occurs because the air intake is blocked with ice, leaves etc. or because the stove 
door was left open, or due to a strong exhaust fan operating, dangerous fumes could be sucked into the 
room.
IN SOME AREAS IT MAY BE REQUIRED TO ELECTRICALLY GROUND THE STOVE TO THE STEEL CHASSIS 
OF THE MOBILE HOME.
When this unit is installed in a Mobile Home it must be grounded to the steel chassis or connected to a 
grounding rod.
Manufactured (Mobile) home installation must be in accordance with the Manufactured Home Construction 
and Safety Standard, UL 307B, Title 24 CFR, Part 3280 and/or The Standard for Manufactured Home 
Installations, ANSI A225.1/NFPA 501A.
WARNING: DO NOT INSTALL IN A MOBILE HOME SLEEPING ROOM.
These connectors must be installed in accordance 
with  the  manufacturer’s  instructions.  Use  only 
specified components. The chimney and pipe must 
extend at least 10 feet (2.4 m) above the stove and 
3 feet (0.9 m) above the highest point of the roof. 
Install a rain cap with spark arrestor at the top that 
will  not  impede  the  smoke  exhaust.  The  chimney 
must be supported at the ceiling or roof so that its 
weight will not sit on the stove. Seal with silicone to 
maintain vapor barrier at the chimney and outside 
air penetrations. 
CAUTION:  THE  STRUCTURAL  INTEGRITY 
OF  THE  MOBILE  HOME  FLOOR,  WALL,  AND 
CEILING/ROOF MUST BE MAINTAINED.
OUTSIDE AIR :
Connection  from  the  stoves  air  intake  to  the 
outside  is  mandatory,  (MOBILE  HOMES  ONLY) 
either  through  a  hole  in  the  wall  not  higher  than 
the  stoves  bottom  or  through  a  hole  in  the  floor 
beneath  the  pedestal,  using  the  fresh  air  adaptor 
provided. If the air intake is through the floor, the 
hole in the pedestal back must be closed with the 
sheet metal cover provided. Avoid cutting any floor 
joists,  wall  studs,  electrical  wiring  or  plumbing. 
Seal around the outside air pipe with insulation to 
prevent  drafts.  Also  install  a  1⁄4”  mesh  rodent  or 
pest screen in the end of fresh-air pipe. Fresh-air 
connection must be of a non-combustible material, 
example:  4”  (10.16  cm)  flexible  aluminum  single 
wall pipe.
Fresh  air  could  also  be  supplied  from  a  vented 
crawlspace.
Installation