Product Description
Components
18
MS-9200UDLS   PN 52750:A    11/04/05
1.6  Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary 
components and wiring interface connectors.  The 4XTMF option module plugs in and 
is mounted to the main circuit board.
Cabinet 
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour).  
Ample knockouts are provided for system wiring.  Also available is an optional dress 
panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for 
Canadian installations).  The dress panel must be installed to meet FM requirements.
Transformer Assembly
One 100VA transformer is provided standard 
with the panel (3.6 amps maximum).  An 
optional 100 VA transformer XRM-24 
(XRM-24E for the MS-9200UDLSE) is 
available to provide maximum system and 
accessory power (6.6 amp total).
Batteries  
The MS-9200UDLS cabinet provides space 
for two batteries (up to 18 Amp Hour).  
Batteries larger than 18 Amp Hour require an 
external charger such as the CHG-75 or 
CHG-120F and a UL listed battery box such 
as the BB-55F.  Batteries must be ordered 
separately.
1.6.1  Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC 
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on 
device installation, wiring and operation).  This allows the control panel to continually 
process the information to determine the status (alarm, trouble, maintenance or normal) 
of each detector.  Each detector responds to an SLC address that is set in the detector 
head using built-in rotary decimal switches.  The maximum address cannot exceed 
address 99.  Note that a blinking LED on an intelligent detector indicates 
communication between the detector and the control panel.  
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface 
Protocol) or LiteSpeed mode to provide a quicker response.  They are also compatible 
with older 300 Series devices.  If a mix of old and new series devices are installed on 
the same loop, the FACP must be programmed to operate in CLIP mode.  Refer to the 
SLC Wiring Manual for a list of compatible addressable detectors.
See Page
Standard
XRM-24(E)
Optional 
XRM-24(E)
9200xf
or
.c
dr
-
-
+
+
Battery Cable P/N 75287
9200batt.cdr