Honeywell MS-9200UDLS Manual Do Utilizador

Página de 188
Components
Product Description
MS-9200UDLS   PN 52750:A    11/04/05
19
1.6.2  Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface 
between the control panel and conventional notification and initiating devices.  Each 
module can be set to respond to an address with built-in rotary switches.  The maximum 
address cannot exceed address 99.  Note that a blinking LED on an addressable module 
indicates communication between the module and the control panel.  
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface 
Protocol) or LiteSpeed mode to provide a quicker response.  They are also compatible 
with older 300 series devices.  If a mix of old and new series devices are installed on the 
same loop, the FACP must be programmed to operate in CLIP mode.  Refer to the SLC 
Wiring Manual for a list of compatible addressable modules.  Refer to the Device 
Compatibility Document for a list of approved conventional notification and initiating 
devices.
1.6.3  300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the 
MS-9200UDLS FACP.  The address of 300 Series devices cannot be set above 99.  
Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.6.4  Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module 
documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-
wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada.  
An ELR, which is supplied with each module and fire alarm control panel, is mounted 
to the ELR plate.  Resistors mounted to the N-ELR plate can be used for the supervision 
of a monitor and control module circuit.
Reference
Manual