Honeywell MS-9200UDLS Manual Do Utilizador

Página de 188
Programming
Master Programming Level
50
MS-9200UDLS   PN 52750:A    11/04/05
If no detectors have been installed on the loop, the following will be displayed: 
If the selected address has been added to programming, device summary screens 
will be displayed.  These screens allow the programmer to view all device settings 
at a single glance.  Pressing the left or right arrow keys will allow the programmer 
to rapidly view the devices at the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not 
physically installed on the SLC or has a communication fault but the address is 
programmed in the system, the following screen will be displayed: 
If the selected address has been added to programming and a detector (such as a 
photoelectric detector) with the selected address is physically installed on the SLC 
and is communicating with the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keyboard ‘down’ 
arrow key to view the Edit Detector screens
.  
In the preceding example:
Normal - indicates that the detector with the selected address is physically 
installed on the SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been 
programmed, describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is 
assigned to (NNN = the three digit zone number from 000 - 099)
V or * - indicates whether or not alarm verification is enabled (V = alarm 
verification enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, 
D=Detector and 017 = Detector Address 017)
    NO DETECTOR
     INSTALLED
Edit Detector Screen #1  
 TROUBL SMOKE(PHOTO)
 <ADJ><NOUN>
               ZNNN
          *    1D017
Edit Detector Screen #1  
 NORMAL SMOKE (PHOTO)
 <ADJ><NOUN>
                ZNNN
            V   1D017
Edit Detector Screen #1