Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
NFPA Standard-Specific Requirements
Correlations
176
MS-9200UDLS   PN 52750:A    11/04/05
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP3 on the MS-9200UDLS main circuit board to supervise placement 
of the 4XTMF module.
2. Refer to  "4XTMF Transmitter Module Installation" on page 38 for detailed 
information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver 
Model RS82.
+        -
Polarity Shown is 
Normal Standby
4XTMF Transmitter Module
Cutting TBL Jumper allows the 
reverse polarity circuit to open 
with a system trouble condition 
if no alarm condition exists.
Power-limited
Figure C.2 Remote Station Connection Using 4XTMF Module
  -
(Dummy load with a 4.7K
Ω, ¼ watt 
resistor when no connection is made)