Wire Requirements
Correlations
178
MS-9200UDLS   PN 52750:A    11/04/05
APPENDIX D 
 
Wire Requirements
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations.  The 
total resistance of any branch cannot exceed 40 ohms.  The total wire length of all 
branches cannot exceed 10,000 feet (3,000 m).
Connecting external system accessories to the MS-9200UDLS main circuits must be 
carefully considered to ensure proper operation.  It is important to use the correct type 
of wire, wire gauge and wire run length for each MS-9200UDLS circuit.  Reference the 
chart below to specify wire requirements and limitations for each MS-9200UDLS 
circuit.
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the 
risk of encountering problems can be greatly reduced by exclusively employing 
electronic sounders (such as MA/SS-24D) instead of more electronically noisy 
notification appliances such as electromechanical bells or horns.
Table D.1  MS-9200UDLS Wire Specifications
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Circuit Type
Circuit Function
Wire Type and Limitations
Recommended 
Max. Distance
Feet (meters)
Wire Gauge and Compatible Brands
SLC loop
(power-limited)
Connects to 
Addressable 
Devices
Twisted pair, 40 ohms 
maximum per length of 
Style 6 and 7 loops.  40 
ohms per branch maximum 
for Style 4 loops
1
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)
12 AWG (3.1 mm
2
): Genesis WG-4315, 
WG-4515, Belden 5020UL, 6020UL
14 AWG (2.00 mm
2
):Genesis WG-4313, 
WG-4513, Belden 5120UL, 6120UL
16 AWG (1.30 mm
2
): Genesis WG-4311,
WG-4511, Belden 5220UL, 6220UL
 18 AWG (0.78 mm
2
): Genesis WG-4306,
WG-4506, Belden 5320UL, 6320UL
Untwisted, unshielded pair
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm
2
)
ACS/TERM 
(EIA-485)
(power-limited)
Connects to 
annunciator 
modules
Twisted, shielded pair with a 
characteristic impedance of 
120 ohms
6,000 (1,800 m)
18 AWG (0.75 mm
2
)
EIA-232
(power-limited)
connects to 
remote printer 
and PC computer
Twisted, shielded pair
50 (15 m)
18 AWG (0.75 mm
2
) minimum
MMF-300 and 
MMF-301
(power-limited)
Initiating Device 
Circuit
Maximum loop wire 
resistance is 40 ohms for the 
MMF-300 and 20 ohms for 
the MMF-301
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2
)
MMF-302
(power-limited)
Initiating Device 
Circuit
No more than a 2.4 volt drop 
allowed at end of circuit.  
Maximum loop wire 
resistance is 25 ohms
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2
)
CMF-300
(power-limited)
Notification 
Appliance 
Circuit
In alarm, no more than a 1.2 
volt drop allowed at end of 
circuit
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm
2
)
24 VDC 
filtered 
resettable
(power-limited)
Connects to 
4-wire smoke 
detectors
No more than 1.2 volt drop 
allowed from supply source 
to end of any branch
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm
2
)
24 VDC 
nonresettable
(power-limited)
Connects to 
control modules, 
annunciators and 
accessories
No more than 1.2 volt drop 
allowed from supply source 
to end of any branch
Distance limitation 
set by 1.2 volt 
maximum line 
drop
12-18 AWG (3.25 - 0.75 mm
2
)
CHG-120F or 
CHG-75
Remote 
secondary power 
source
12 AWG (3.25 mm
2
) in 
conduit
20 (6 m)
12-18 AWG (3.25 - 0.75 mm
2
)
Table Footnote
1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.