The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secondary) from the FACP before installing 
4XTMF
2. Cut jumper JP3 on the main circuit board to allow the control panel to supervise 
the 4XTMF module
3. Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 
on the MS-9200UDLS main circuit board, being careful not to bend any pins 
4. Secure 4XTMF module to standoffs with supplied screws.  
5. Reapply power to the FACP
6. For proper 4XTMF operation, the output relays must be programmed for the 
factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
7. When the installation has been complete, enable the 4XTMF module by sliding 
the disconnect switch to the left
8. Test system for proper operation
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP 
supervisory relay for operation with the 4XTMF module.  Relay 3 at TB5 must be 
programmed as a supervisory relay.
Cutting JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens
Leaving JP2 in will prevent generation of a trouble if the supervisory contact opens
RELAY 1
CUT TO
MONITOR
4XTMF
KISSOFF
PRI. ACTIVE
SEC. ACTIVE
SEC. PHONE LINE
PRI. PHONE LINE
4XTMF
RELAY 2
NO NC   C
NO NC   C
B+   A+   B-   A-     A     B
ACS
SHIELD
SLC
SLC
SLC
SLC
OUT+ IN+ OUT- IN-
TB5
TB6
TB8
TB9
TB10
JP1
JP2
JP3
1   2   3
J13
J12
J7
J5
J6
Figure 2.16 4XTMF Connectors to MS-9200UDLS Connectors