Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Optional Module Installation
Installation
MS-9200UDLS   PN 52750:A    11/04/05
41
2.9.3  Digital Communicator and Annunciators
2.9.3.1  ACM-8RF Relay Control Module
The ACM-8RF module provides eight Form-C relays with contacts rated for 5 
amps.  When installed with an MS-9200UDLS FACP, the ACM-8RF modules 
provide relay activation for each of the 99 possible FACP zones plus special 
functions.  Options exist to allow for alarm only or alarm and trouble activation per 
zone.  Output activation for general alarm, general trouble, general supervisory, 
NAC fault, AC fail, walktest start and battery trouble are also available.  The ACM-
8RF can be mounted remotely in an ABS-8RF annunciator surface-mount backbox.  
Refer to the ACM-8RF manual for information on setting module switches for 
addressing and relay functions.
2.9.3.2  ACS and AFM Series Annunciators
ACS and AFM Series Annunciators provide visual indications of FACP status in 
remote locations.  Refer to the appropriate annunciator manual for information on 
installation, wiring and operation.  
Annunciator addressing is specific to the MS-9200UDLS control panel.  The 
following table describes the annunciator addresses and the corresponding 
addressable devices that will be annunciated at each annunciator address. 
The MS-9200UDLS must be programmed for the annunciators installed on the 
system.  Refer to  "Annunciators/UDACT" on page 96 for information on 
annunciator programming.  Make certain to program the annunciator addresses that 
have been physically installed on the system.
Note: The 8 General System Status Points include the following:
Reference
Manual
ACM Annunciator Address
Annunciator Displays the Following Points
1
8 General System Status Points & Zones 1 - 56
2
Zones 57 - 99 & 4 NACs
3
SLC Loop, Module Addresses 1 - 64
4
not used
5
SLC Loop, Module Addresses 65 - 99
6
not used
7
not used
8
SLC Loop, Detector Addresses 1 - 64
9
not used
10
SLC Loop, Detector Addresses 65 - 99
11
not used
12
not used
13
not used
14
not used
15
not used
16
not used
17
not used
18
not used
19
not used
20
8 General System Status Points & Zones 1 - 56
21
Zones 57 - 99 & 4 NACs
22
SLC Loop, Module Addresses 1 - 64
23
not used
24
SLC Loop, Module Addresses 65 - 99
25
not used
26
not used
27
SLC Loop, Detector Addresses 1 - 64
28
not used
29
SLC Loop, Detector Addresses 65 - 99
30
not used
31
not used
32
not used
• General Alarm
• Alarm Silenced
• Battery Fault
• General Trouble
• System Off Normal
• NAC Fault
• General Supervisory
• AC Loss