Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Master Programming Level
46
MS-9200UDLS   PN 52750:A    11/04/05
3.6  Master Programming Level
When the Master Program Level password is entered, the control panel will enter user 
Programming mode.  In this mode, the piezo sounder remains off, the trouble relay is 
activated and the system Trouble LED flashes until Programming mode is exited.  The 
following display will appear: 
The down arrow which appears in the display indicates that additional programming 
choices can be viewed by pressing the down arrow key on the keypad.  If a down and 
up arrow appear in the display, pressing the ‘down’ arrow key will display the 
subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow 
key will display the previous screen.
 
    PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1  
    PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
    PROGRAMMING
1=HISTORY
2=WALKTEST
3=OPTION MODULES
    PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #2  
Programming Screen #3  
Programming Screen #4