Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Master Programming Level
62
MS-9200UDLS   PN 52750:A    11/04/05
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing the Edit 
Module Screen #2.  Each press of the key will toggle the screen between Enabled 
Yes
 and Enabled No.  If Enabled No is selected, the module will not be polled by the 
control panel, preventing the module from reporting alarms and troubles to the 
panel.  The control panel will indicate a system trouble condition and the Disable 
LED with turn on if any devices are disabled.
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor 
types can be created and loaded into the FACP for later use.  The FACP response to 
the activation of a user-defined type is the same as most previous standard types in 
the list, thus allowing a variety of user-defined types and responses.  To select the 
type of monitor module being programmed, press the 2 key while viewing the Edit 
Monitor Screen #2.  This will cause the control panel to display the following 
Monitor Type Screens:  
Pressing the down arrow key will display additional Monitor Type screens.  While 
viewing one of the Monitor Type screens, select the type of monitor module being 
programmed by pressing the corresponding keypad number key.  The display will 
return to the Edit Monitor Screen #2 which will show the new type selection.
Table 3.1 on page 63 lists the Monitor Types and their respective functions.
EDIT MONITOR
1=ENABLED
2=TYPE  MONITOR
Edit Monitor Screen #2
   MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1