Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Master Programming Level
Programming
MS-9200UDLS   PN 52750:A    11/04/05
63
Monitor module type selection will affect the function of the point as follows: 
Note: 
1. For the PROCESS-MONITOR-AR selection, AR refers to AutoResettable
2. For HVAC RESTART and HVAC OVRRIDE descriptions, refer to  "Monitor 
Module Operation" on page 179
Table 3.1  Monitor Types
Monitor Type 
Action When Activated
Pull-Station
Fire Alarm
User-Defined-1
same as previous (Pull-Station)
Waterflow
Fire Alarm Delayed
User-Defined-2
same as previous (Waterflow)
Monitor
Fire Alarm
User-Defined-3
same as previous (Monitor)
Future
not used
Future
not used
Smoke-Conventional
Fire Alarm
User-Defined-5
same as previous (Smoke-Conventional)
Heat-Conventional
Fire Alarm
User-Defined-6
same as previous (Heat-Detector)
Medic-Alert Supervisory, 
latching
User-Defined-7
same as previous (Medic-Alert)
Hazard-Alert
Supervisory, latching
User-Defined-8
same as previous (Hazard-Alert)
Tornado-Alert
Supervisory, latching
User-Defined-9
same as previous (Tornado-Alert)
Future
not used
Future
not used
Tamper
Supervisory, nonlatching (tracking)
User-Defined 11
same as previous (Tamper)
Supervisory
Supervisory, latching
User-Defined 12
same as previous (Supervisory)
Supervisory-AR
Supervisory, nonlatching (tracking)
User-Defined 13
same as previous (Supervisory-AR)
Power-Monitor
Power Fault
User-Defined 14
same as previous (Power Monitor)
Trouble-Monitor
Trouble
User-Defined-15
same as previous (Trouble Monitor)
Process-Monitor
Piezo
User-Defined 16
same as previous (Process-Monitor)
Process-Monitor-AR
Piezo, nonlatching (tracking)
User-Defined-17
same as previous (Process-Monitor-AR)
Future
not used
Future
not used
Ack-Switch
Acts like panel Acknowledge Key
Sil-Switch
Acts like panel Silence Key
Reset-Switch
Acts like panel Reset Key
Drill-Switch
Acts like panel Drill Key
PAS-Bypass
PAS Disable
HVAC RESTART
Switch
HVAC OVRRIDE
Switch
Drill-Switch-AR
Acts like panel Drill Key, nonlatching (tracking)