Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Master Programming Level
86
MS-9200UDLS   PN 52750:A    11/04/05
3.6.5.4.4  AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by 
programming the length of the desired delay.  Press 1 while viewing Timer Screen 
#2 to display the following: 
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to 
transmit an AC Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
A flashing cursor will appear in the lower left corner of the display.  Type the two 
digit AC loss reporting delay in hours (00 to 23 hour delay).  When the second digit 
is entered, the display will return to AC Loss Delay Screen #1.
Important: For Central Station applications, AC Loss Reporting Delay must be set 
to a delay value ranging from 06 to 12 hours.  For Remote Station applications, AC 
Loss Reporting Delay must be set to a delay value ranging from 15 to 23 hours.
Note:  AC Loss Delay also applies to any programmable output relay programmed 
for ‘AC Loss.’
3.6.5.5  NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure 
by pressing 2 while viewing System Setup Screen #2.  The following screens will 
be displayed:
The Notification Appliance Circuits can be configured independently by pressing 1 
for NAC 1, 2 for NAC 2, 3 for NAC 3 or 4 for NAC 4.  
Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed, 
regardless of how the NACKEY card is installed.  Their programming, however, will 
have no effect if the NACKEY card is installed for Class A operation.
   TIMER
1=AC LOSS DELAY
Timer Screen #2
 AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1  
 AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2  
   SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
       NACS
1=NAC 1      3=NAC 3
2=NAC 2      4=NAC 4
NAC Selection Screen