Honeywell MS-9200UDLSE Manual Do Utilizador

Página de 188
Programming
Master Programming Level
88
MS-9200UDLS   PN 52750:A    11/04/05
3.6.5.5.2  Type
The main circuit board NAC type can be programmed by pressing 2 while viewing 
NAC Screen #1.  The following screen will be displayed.  Press the down arrow key 
to view additional screens:
Select the NAC device type by pressing the number corresponding to the type in the 
appropriate screen.  When the selection is made, the display will return to NAC 
Screen #1.
The following table contains NAC type codes and their functions:
3.6.5.5.3  Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to 
Silenceable No.  This will prevent the selected main circuit board NAC from being 
silenced by pressing the Alarm Silence key or by the Auto Silence feature.  Each 
press of the 3 key will cause the display to toggle between Silenceable Yes and 
Silenceable No
Important:  When a Notification Appliance Circuit with a mix of audible and visual 
devices is programmed for silenceable and the Synced Strobe feature is selected, 
only the audible devices will be turned off if the Silence key is pressed or if the 
Autosilence feature is enabled.  The visual devices (strobes, etc.) will continue to 
operate.  If the Strobe Sil Sync feature is selected, Silence or Autosilence will turn 
off both audible and visual devices.
NAC Type Code
Special Function
Bell
None
Horn
None
Strobe
None
Synced Strobe
Synchronized to manufacturer
Strobe Sil Sync
Same as Synced Strobe but Silence turns off audible & visual devices
Siren Circuit
None
   NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
       NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen  #1