Honeywell MS-2 Manual Do Utilizador

Página de 56
Installation
Output Circuits
22
MS-2/MS-4   PN 51512:E  01/18/05
2.4  Output Circuits
2.4.1  Notification Appliance Circuits
The MS-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while 
the MS-4 provides two Style Y (Class B) NACs.  Each circuit is capable of providing a 
maximum of 2.5 amps of current.  Total current drawn from these as well as other DC 
power outputs cannot exceed 3.0 amps for the MS-2 or 6.0 amps for the MS-4 with the 
optional second transformer installed (refer to battery calculations section). Each circuit 
is supervised and power-limited.  Refer to the Fire•Lite Device Compatibility 
Document for a listing of compatible notification appliances.
The MS-4 NACs can be converted to Style Z (Class A) by installing the optional Class 
A Converter module.  Refer to  "CAC-4 Class A Converter Module (MS-4 only)" on 
page 25.
TB2
B+   B-     B+    B-
 NAC 1    NAC 2
Figure 2.6 NAC Connections
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K
Ω
, ½ watt resistor P/N:71252
Dummy load any unused 
circuits (P/N: 71245)
Polarized Bell
Polarized Strobe
Polarized Horn
Polarized Horn
Polarized Horn-Strobe
Polarized Bell
Notification Appliance Circuit 
polarity shown in alarm condition
ms-4nac
.cdr