2.4.2  Special Application DC Power Output Connections
Resettable 24 VDC special application power is available on both the MS-2 and MS-4 
control panels.  Nonresettable 24 VDC special application power is available only on 
the MS-4. 
2.4.3  Relays
The MS-2 and MS-4 control panels provide an alarm and fail-safe trouble relay and the 
MS-4 also provides a supervisory relay.  Each Form-C relay is rated for 2 amps @ 
30VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that 
0.25” minimum spacing is maintained between conductors of power-limited and 
nonpower-limited circuits.
TB1
Figure 2.7 Special Application Power
4-Wire Smoke Detector Power (500 mA) 
24 VDC filtered, resettable special application power 
for 4-wire smoke detectors can be obtained from 
these terminals (power-limited)
Nonresettable Power (500 mA) - MS-4 Only
24 VDC filtered, nonresettable special 
application power can be obtained from 
these terminals (power-limited)
+      -      +      -
ms-4tb1.cdr
TB
5
TB
6
TB
7
   TROUBLE
C  TRBL NORM
C     NC   NO
ALARM
SUPV
C     NC   NO
Figure 2.8 Relay Terminals
Note:  Relay contacts are shown with 
power applied to the panel and no active 
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay 
which will transfer on any trouble or 
total power failure.