Honeywell MS-2 Manual Do Utilizador

Página de 56
Installation
Installation of Optional Modules
30
MS-2/MS-4   PN 51512:E  01/18/05
2.6.2.3  4XLMF LED Interface Module (MS-4 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module.  The wiring of this 
module must follow the requirements as specified in  "Power-limited Wiring 
Requirements" on page 24.  
Important:  The 4XLMF module can only be installed on connectors J3 and J5 of the 
MS-4 main circuit board
.
4XLB
Figure 2.15 4XLMF LED Interface Module
Front View of RZA-4XF
Side View
Single-gang Box
4XLMF Module
Note: Make wiring connections with 
system power off.  Maximum 
wire impedance is 50 ohms per 
wiring connection.
+24 VDC
Out #1
Out #2
Out #3
Out #4
System Trouble
Sound
Resound
2
3
4
5
6
7
8
Connect to corresponding terminals 
of RZA-4XF Remote Annunciator
4xlma.cdr
rz
a-4xf
r.cdr
rz
a-4xbx.c
dr