2.6.2.1  4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter 
in addition to alarm and trouble reverse polarity.  A jumper option allows the reverse 
polarity circuit to open with a system trouble condition if no alarm condition exists.  A 
disable switch allows disabling of the transmitter output during testing to prevent 
accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended 
for connection to a polarity reversal circuit or a Remote Station receiving unit 
having compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) 
position to prevent accidental activation of the municipal box.  Note that a Disconnect 
LED will illuminate after the module is installed in the FACP.  In addition, the System 
Trouble LED will turn on to indicate the Disconnect condition. 
TB1
TBL
J1
J2
Figure 2.13 4XTMF Transmitter Module
Connect to: 
• MS-4 Connectors J3 & J5 or J4 & J6
• MS-2 Connectors J3 & J5.
Disconnect 
Switch 
shown in 
disconnect 
position
TBL Jumper
}
Remote Alarm (power-limited)*
}
Remote Trouble (power-limited)*
     No connection
}
Municipal Box (nonpower-limited)*
1+
2-
3+
4-
5
6+
7-
Polarities are shown for module activation
Note: 4XTMF Module is not suitable for 
transmitting reverse polarity supervisory signal.
* Wiring from these terminals can 
exit the protected premises.  
Dummy load terminals 6 and 7 
(4.7k
Ω, ¼ watt resistor) if 
Municipal Box is not connected.
Disconnect LED
4xtmf.c