Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
139
Maintenance Programming Level
Programming
Note that in the preceding screens, an arrow appears to inform the programmer that additional 
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.
3.7.1  Disable Point
Pressing 1 for Point Program, while viewing Maintenance Screen #1 will cause the following 
screens to be displayed:
Select the Loop, containing the device to be disabled, by pressing 1 for Loop 1 or 2 for Loop 2.  A 
screen will then be displayed, allowing the operator to select the type of addressable device to be 
disabled as shown in the following display:
Select the device type by pressing 1 for an addressable detector or 2 for an addressable module.  
The operator will be prompted to enter the three digit device address as shown in the following 
example for a detector:
    PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
    PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
  POINT PROGRAM
1=LOOP 1
2=LOOP 2
Loop Select Screen 
  POINT PROGRAM
1=DETECTOR
2=MODULE
Device Select Screen 
 EDIT DETECTOR
ENTER POINT ADDRESS
***
Address Select Screen