Honeywell MS-9600LSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
141
Maintenance Programming Level
Programming
Pressing 2 while viewing the History Screen will cause the following screen to be displayed: 
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, 
PLEASE WAIT
 to be displayed.  The display will then return to the History Screen.  Pressing 2 will 
cause the display to return to the History Screen without erasing the History file.
3.7.3  Program Check
Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
The Program Check feature allows the programmer to view the zones which have been pro-
grammed to the Notification Appliance Circuits on the control panel but have not been pro-
grammed to Initiating Devices as well as other circuits with no input or output correlations.  
Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be 
displayed. 
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55, and 67 but 
no input devices have been programmed to any of these zones.  Use the up and down arrow keys to 
view all the NAC zones without input assignments for NAC1, NAC2, NAC3, and NAC4.
   ERASE HISTORY
     PROCEED ?
1=YES            2=NO
Erase History Screen 
    PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
    PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen 
   NACS NO INPUT
NAC 1
    25 31 44 55 67
NOTE: If the NACs have been configured for Class A in the Setup option, only NAC1 and NAC2 will 
display test information.  NAC3 and NAC4 will display asterisks (*) and will not be included in the test.