MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Appendix B: Default Programming
The following table provides a list of the programming options and their factory default settings. 
Program Option
Factory Default
Program Option
Factory Default
Master Password
00000
NAC Enable
Enabled
Maintenance Password 
11111
NAC Silenceable
Yes
Detector Programming
Not Installed
NAC Type
Bell
Detector Type
Smoke-Photo
NAC Sync Type
System Sensor
Detector Verification
Off
NAC Autosilence
0
Detector Walktest
Yes
NAC Coding
Steady
Detector PAS
No
NAC Zones
Zone 000 only 
Detector Presignal
No
NAC Silence Inhibit
0
Detector Zone Assign.
000 only
Relay 1
Alarm
Detector Adj/Noun
none
Relay 2
Trouble
Module Programming
Not Installed
Relay 3 
Supervisory
Module Type
Monitor
On Board DACT
No
Module Walktest
Yes
Annunciator Terminal Mode
No
(not used)
Annunciator ACS Mode
No
Module Presignal
No
UDACT
No
Module Zone Assign.
000 only
ACS Installed
No
Module Adj/Noun
none
Printer-PC
No
Zone 0 Enable
Enabled
Printer Baud
9600
Zone 1 Enable
Enabled
Canadian Option
Off
Zone 2 Enable
Enabled
Waterflow Silenceable
No
Zone 3 Enable
Enabled
ANN-BUS Enabled
No
.........................through..........
.....................
Central Station Reporting
Disabled
Zone 99 Enable
Enabled
AC Loss Delay
2 Hours
Special Zones 97, 98 & 99
Disabled
DACT Backup Reporting
First Available
Zones 0 - 99 Type
Monitor
DACT Report Style
By Point
Loop 1 & 2 Style
Style 4
ANN Enabled
No
Loop 1 & 2 Protocol
LiteSpeed
ANN-BUS Modules Addr. 1 - 8
None
Trouble Reminder
Off
ANN-S/PG Port
Parallel
Banner
ANN-S/PG Baud
9600
Time Format
12 Hr
ANN-S/PG Data Bits
7
Hours Setting
12
ANN-S/PG Parity
Even
Minutes Setting
00
ANN-S/PG Stop Bits
1
Second Settings
00
ANN-S/PG Offline Timer
60
AM-PM Setting
AM
ANN-S/PG Printer Supervision
No
Month Setting
01
ANN-80 Piezo Enabled
Yes
Day Setting
01
ANN-80 Lock Enabled
Yes
Year Setting
00
ANN-80 Acknowledge Button Enabled
Yes
PK-Plus Secret Code
00000000
ANN-80 Silence Button Enabled
Yes
Trouble Call Limit
0
ANN-80 Reset Button Enabled
Yes
Daylight Savings
Yes
ANN-80 Drill Button Enabled
Yes
Month Start Daylight Savings
March
ANN-I/O Point/Zone
Zone
Week Start Daylight Savings
2nd Week
ANN-I/O Range
00-29
Month End Daylight Savings
November
ANN-I/O Active LEDs Only
Week End Daylight
1st Week
ANN-RLY Relay 1
Zone 1
Verification
No
................through.......................
............
Ring Count
0
ANN-RLY Relay 10
Zone 10
PAS Timer
0
ANN-LED Point/Zone
Zone
Presignal Timer
0
ANN-LED Alarms/ATS (Alarm, Trbl, Supv)
ATS
Waterflow Retard Timer
0
ANN-LED Range