MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
NFPA Standard-Specific Requirements
NFPA Signaling Systems for Central Station Service (Protected Premises 
Unit)/Remote Station
The following figure illustrates an example of Central Station/Remote Station Reporting using a 
411UDAC. The relay contacts from the FACP may be used to trip any dialer UL listed for Central 
Station/Remote Station Services.  
Notes:
1. Reference the 411UDAC Manual for additional information
2. Program the 411UDAC for slave operation
3. The FACP must be programmed for AC Loss Reporting Delay  This prevents the transmission 
of a trouble on the loss of AC power
TB1
Figure C.1  Central Station Service Using 411UDAC
2.2K
ELR
AC wiring for 
411UDAC/FACP must 
be connected to the 
same branch circuit.
FACP
411UDAC
Al
ar
m
 Re
la
y
Trou
ble R
elay
Supv. Relay
Monitor Module 
ELR resistor
SLC Loop
Monitor Module*
Monitor Module Circuit Input
411UDAC Relay 2 Output (DACT Trouble)
Channel 1/Zone 1
Channel 3/Zone 3
Channel 2/Zone 2
2.2K EOLR
UL listed 2.2K ELRs (P/N 27070)
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact
                   Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
Note: The Monitor Module input, 
which is being used to monitor the 
411UDAC Relay Output 
programmed for DACT Trouble 
(requires optional 411RK Relay Kit), 
must be programmed as ‘Trouble’ at 
the FACP.  The 411UDAC must be 
programmed as a Slave 
Communicator (programming 
address 64 set to 2).
123
 
1 2 3 4 5 6 7 8 9 10
123456
96
0041
1a
.w
mf
*If the SLC device does 
not match the one in this 
figure, refer to the SLC 
manual appendix, which 
contains wiring conversion 
charts for type V and type 
H modules.
411UDAC
FACP
Alarm
TB2-1
TB1-3
TB2-2
TB1-1
Trouble
TB2-3
TB5-3
TB2-4
TB5-2
Supervisory
TB2-5
TB5-6
TB2-8
TB5-4
Table C.1  411UDAC Connections to FACP