IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 
 
– 13 – 
IPGSM-4GC Trouble Detection Information 
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4GC, and Telco 2 is used by the IPGSM-
4GC to report faults to the Fire Panel.  If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if 
there are no faults in the Communicator.  
Fault Condition 
Indication to Fire Panel 
PowerBoost1 fault 
Telco 2 is cut.  
Communicator fault 
 
  Failure of the communications path when 
IP only or GSM only is programmed as a 
communications path. 
Telco 2 is cut. 
  Failure of both communications paths 
when IP&GSM is programmed as a 
communications path. 
Telco 1 and 2 are cut. 
Dialer Capture Module buffer is full. 
Hang up.  (Panel will retry, giving the buffer a chance 
to empty.)   
 
IPGSM-4GC Specifications 
 
ITEM 
SPECIFICATION 
Cabinet Dimensions: 
Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches 
Transformer: 1451-UL9 
Primary – 120VAC, 60Hz, 850mA, Secondary – 18VAC, 72VA 
Battery: 
12V, 7Ah sealed lead acid type (not supplied) 
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.  
Battery Charging Current: 
maximum 1A 
Battery Discharge Current:  standby 230mA, active 950mA 
Environment: 
Operating temperature: –20º to +55ºC, for ULC installations 0ºC to 
+49ºC 
Storage temperature: –40º to +70ºC 
Humidity: 0 to 95% relative humidity, non-condensing, for ULC 
installations 0% to 93% 
Altitude: to 10,000 ft. operating, to 40,000 ft. storage 
Supervision: 
The Radio (communicator), battery, and AC power, conditions  are 
monitored by the cabinet indicator LEDs: 
RADIO TROUBLE lights when any of these conditions exist. 
 
Both IP and GSM communication paths are lost. 
 
Communicator radio is not registered. 
 
Old Alarm Time has been exceeded.  (Message has not been 
delivered within the fixed 10 minute window.)  
LOW BATTERY lights when the battery voltage is less than 11.5VDC. 
AC LOSS lights when the AC power is less than 90VAC.