Honeywell IPGSM-4GC Manual Do Utilizador

Página de 24
IPGSM-4GC Commercial Fire Communicator – Installation and Setup Guide 
 
– 11 – 
Communicator Information 
 
TB 1
6
7
8
5
10
11
9
2
3
4
1
IPGSM-4GC-012-
V
0
RSSI / Mode
and
status LEDs
ON – Message transmission pending.
QUICK PERIODIC BLINK – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle power abnormal.
SLOW BLINK – In unison with green LED,
                          registration in progress.
Ethernet Link/Activity
GREEN 
ON  –  Link detected.
OFF – No link detected.
FAST BLINK – Network activity.
Link Speed
GREEN 
Note: If all LEDs FAST BLINK in unison with
          the RSSI LEDs this indicates a Hardware Error.
ON – No contact with network.
OFF – Normal.
SLOW BLINK – Loss of communication with the
                       Dialer Capture Module
 (ECP fault).
ON – NOT registered with AlarmNet.
OFF – Registered with AlarmNet.
FAST BLINK – Download session with Compass
                         in progress.
SLOW BLINK – In unison with yellow LED,
                          registration in progress.
Mode
Switch
Tamper
Switch
GRN
YEL
RED
7720P
Programmer
Port
ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.
FAST BLINK – No network contact AND loss of communi-
                        cation with the 
Dialer Capture Module
.
MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)
When the Mode Switch is NOT depressed, LED 1 will illuminate red.
The remaining LEDs indicate RSSI (Received Signal Strength).
MODULE'S OPERATION MODE
When the Mode Switch IS depressed, LED 1 will be OFF.
   LEDs 2 and 3 indicate the  module's communication mode with the control panel.
Mode                                LED 2 (yellow)                        LED 3 (yellow)
When the Mode Switch IS depressed, LED 1 will be OFF.  
  LEDs 4, 5, and 6 indicate the module's Status.
FAST BLINK - Module registered,
second site available, excellent
signal strength.
LED 4 (green)                     LED 5 (green)                           LED 6 (green)
ON - Connected to
Internet.
ON - Module registered, no second
site available.
ON - GPRS service
available.
OFF - No GPRS service
available.
OFF - Module not registered with
network carrier.
FAST BLINK - GPRS in
use.
SLOW BLINK - Module registered,
second site available, and low signal
strength.
NORMAL BLINK - Module registered,
second site available, acceptable
signal strength.
OFF - Not connected
to Internet.
MODULE'S STATUS
ECP                                                          OFF                                         OFF
Zone                                                         ON                                           OFF
4204                                                         OFF                                         ON
2 - 4204                                                    ON                                           ON
Cellular Status LED
Voice Session  –
Short blink every second
Data Session  –
Short blink every 2 seconds
Connected to Cell network –
Short blink every 4 seconds
No or deactivated SIM –