Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (07/08)
HA40 Technical Manual
2-8
Over Ride
 menu allows entering one of the 16 different alarms 
that will trip this relay regardless of the Votes entries.  There 
are four alarms per channel and four channels and any one of 
these alarms may be used as the Over Ride.  This feature is 
useful when one channel’s alarm has more significance than 
the others.
Horn
 controls how activating this relay will affect the horn driver 
circuit connected to J2 on the motherboard.  Choices are NO, 
STEADY  or  PULSE.   Warning  level  alarms  might  be  set  to 
pulse the horn and high alarms set for steady.  Personnel can 
then know which alarm level is present by hearing the pulsing 
or steady horn.
Turning Acknowledge ON (not allowed on Relay 1) allows Relay 
• 
2 to be deactivated during alarm conditions by an Alarm Reset.  
This is useful if another audible device is being driven by the 
relay.  The acknowledge feature is not available for Relay 1 since 
it is often used for driving a warning light and Relay 2 for driving 
a horn.  It could be dangerous if an operator acknowledged 
the horn AND the light since no indication of the high alarm 
condition would remain.
2�3�2 Clock / Delays Menu
The  HA40  monitors  signals  from  inputs  that  may  require  varying 
times  to  stabilize  after  power  is  applied  and  after  calibrations  are 
complete.
Alarm  Refresh
  menu  allows  reactivation  of  Acknowledged 
alarms  after  the  time  period  expires.   This  feature  is  used 
primarily  to  restart  audible  alarm  devices  after  having  been 
silenced by an acknowledge function (via serial port or pressing 
the  Alarm  Reset  button).    An  entry  of  0  seconds  effectively 
disables the Alarm Refresh function.
Warm-Up Delay
 menu allows setting how long alarm relays 
remain disabled after power is applied.
Cal Delay
 determines how long alarm relays are inhibited after 
completing a calibration.
Time
 and 
Date menu items are for setting the correct time and 
date.  The HA40 is equipped with a 24-hour clock and calendar.  
Time of day must be entered in 24 hour mode.  For example, 
6:00:00 PM = is indicated as18:00:00.
Figure 2-9. Clock/Delays Menu
2�3�3 COMM Port Remote ID Menu
The  system  Remote  ID  menu  allows  setting  RTU  address  for  the 
optional slave Modbus serial port (requires 10-0253 Modbus option 
PCB – see Section 3.2).  This slave port may be used to transfer HA40 
data to a host device such as a PC, PLC, DCS or even other Honeywell 
Analytics controllers, such as the 16 Channel HA71.  The slave port 
is addressable, allowing many HA40 controllers to be connected to a 
single RS-485 cable.  A converter is available to make this port also 
compatible with Ethernet TCP/IP networks.
Figure 2-10. COMM Port ID Remote Menu