Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (08/08)
HA40 Technical Manual
3-8
CHAN1 FAULT
CHAN1 ALARM1
CHAN1 ALARM2
CHAN1 ALARM3
CHAN2 FAULT
CHAN2 ALARM1
CHAN2 ALARM2
CHAN2 ALARM3
CHAN3 FAULT
CHAN3 ALARM1
CHAN3 ALARM2
CHAN3 ALARM3
CHAN4 FAULT
CHAN4 ALARM1
CHAN4 ALARM2
CHAN4 ALARM3
BIT0
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
BIT9
BIT10
BIT11
BIT12
BIT13
BIT14
BIT15
LED Blink Status
31011
4
NA
Bit set to 1 = LED Blinking, bit set to 0 = LED is steady ON.
CHAN1 FAULT
CHAN1 ALARM1
CHAN1 ALARM2
CHAN1 ALARM3
CHAN2 FAULT
CHAN2 ALARM1
CHAN2 ALARM2
CHAN2 ALARM3
CHAN3 FAULT
CHAN3 ALARM1
CHAN3 ALARM2
CHAN3 ALARM3
CHAN4 FAULT
CHAN4 ALARM1
CHAN4 ALARM2
CHAN4 ALARM3
BIT0
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
BIT9
BIT10
BIT11
BIT12
BIT13
BIT14
BIT15
Relay Status
31012
4
NA
Bit set to 1 = LED Blinking, bit set to 0 = LED is steady ON.
STANDARD RELAY 1
STANDARD RELAY 2
OPTION RELAY 1
OPTION RELAY 2
OPTION RELAY 3
OPTION RELAY 4
OPTION RELAY 5
OPTION RELAY 6
INPUT FAULT RELAY
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
BIT0
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
BIT9
BIT10
BIT11
BIT12
BIT13
BIT14
BIT15
VARIABLE
ALIAS
READ 
FUNCTION 
CODE
WRITE 
FUNCTION 
CODE
Memory Reals:
Notes:  41001 – 41040 “Real” represents float value without the decimal point such 
that 123.4 is returned as 1234.  Decimal devisor is returned as 1, 10, 100, or 1000 for 
decimal position of 1, 2, 3, or 4, where 123.4 would return the devisor value 10.
Chan 1 Zero Real
41001
3
NA
Chan 1 Zero Divisor
41002
3
NA
Chan 1 Span Real
41003
3
NA
Chan 1 Span Divisor
41004
3
NA
Chan 1 Alarm 1 Real
41005
3
NA
Chan 1 Alarm 1 Divisor
41006
3
NA
Chan 1 Alarm 2 Real
41007
3
NA