Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (08/08)
HA40 Technical Manual
3-6
3�2 MODBUS RS-232 / RS-485 Interface Option
(P/N 10-0253)
The  10-0253  Modbus  option  PCB  add  both  RS-232  and  RS-485 
Modbus  RTU  slave  ports.    Figure  3-7  shows  this  optional  PCB, 
which mounts to connectors on the upper right corner of the HA40 
motherboard.  TB1 provides two pairs of T/Rx terminals and a floating 
terminal  for  shield  continuation.   This  makes  it  easy  to  multi-drop 
HA40s onto an RS-485 cable without doubling wires into the same 
screw terminals.  RS-232 interface may be made by connecting to 
DB9 connector S1.  
Section 3.3.1
 lists all modbus registers and their 
function codes.
 Caution
Follow correct IEEE RS-232 and RS-485 installation guidelines when 
using the 10-0253 option.
Figure 3-7. HA40 Modbus Interface Option (P/N 10-0253)
3�2�1 MODBUS Register And Function Code 
Summary
The  following  table  identifies  the  available  modbus  RTU  register 
locations and function codes.
VARIABLE
ALIAS
READ 
FUNCTION 
CODE
WRITE 
FUNCTION 
CODE
Read/Write Coils:
Alarm Ack/Reset
2001
1
5
note:
After writing a TRUE to this register, the HA40 automatically returns it to 
FALSE.
Read Only Discrete:
Chan 1 Fault Alarm
12001
2
NA
Chan 1 Alarm 1
12002
2
NA
Chan 1 Alarm 2
12003
2
NA
Chan 1 Alarm 3
12004
2
NA
Chan 2 Fault Alarm
12005
2
NA
Chan 2 Alarm 1
12006
2
NA
Chan 2 Alarm 2
12007
2
NA
Chan 2 Alarm 3
12008
2
NA
Chan 3 Fault Alarm
12009
2
NA
Chan 3 Alarm 1
12010
2
NA
Chan 3 Alarm 2
12011
2
NA
Chan 3 Alarm 3
12012
2
NA
Chan 4 Fault Alarm
12013
2
NA
Chan 4 Alarm 1
12014
2
NA
Chan 4 Alarm 2
12015
2
NA
Chan 4 Alarm 3
12016
2
NA