Honeywell HA40 Manual Do Utilizador

Página de 39
HA40 4-Channel Controller
Revision 1 (08/08)
HA40 Technical Manual
1-2
1 General Description
The Honeywell Analytics HA40 Quad Channel Controller is designed 
to display, and control alarm event switching for four inputs.  Inputs 
are typically voltage or 4-20mA current from transmitters, monitors or 
other analog output devices.  The HA40 is equipped with a Fault and 
three alarm levels per channel with features such as ON / OFF delays, 
latching relays and alarm Acknowledge.  A dedicated horn driver circuit 
for a local audible annunciator is also standard.  Two standard 5-amp 
alarm relays are configurable via the “alarm voting” menu to make 
relays trip based on various alarm combinations.  A real-Time Clock 
and Calendar are also standard. Options such as 4-20mA outputs, 
discrete relays for each alarm and audible annunciators are easily 
added.  RS-485    (Modbus RTU) or  Ethernet (Modbus TCP)  ports 
are also available for sending data to PC’s, PLC’s, DCS’s, or other 
Honeywell Analytics controllers.
A 128 x 64 pixel graphic LCD readout displays monitored data as bar 
graphs, 30-minute trends and engineering units.  System configuration 
is via user friendly menus and all configuration data is retained in non-
volatile memory during power interruptions.  The HA40 front panel is 
shown in Figure 1-1 displaying the bar graph data screen.  The five 
keypad symbols below the display are magnetically activated using 
the supplied magnetic wand without opening the enclosure.  Opening 
the enclosure door provides access to the keypad buttons as shown 
in Figure 1-2.
    
ALARM 1
ALARM 2
ALARM 3
COMMON
LEVEL
ALARMS
KEYPAD
CAL IN PROGRESS
FAULT ALARM
Magnetic
Keypad
(Keypad buttons
behind door)
HA40 Display & Alarm Controller
STATUS
LED's
Quad Channel
Edit
Alarm
Reset
Next
219995
Classified to CSA C22.2 NO. 152 for combustibles
detection. Class I, DIV.2, Groups A,B,C,D
READ & UNDERSTAND MANUAL!
S/N 90-
or 10-30 VDC @ 3 WATTS
Power = 100-240 V~, 50/60 Hz, .45 A
Figure 1-1. Front Panel
   
SW1-SW5 are the magnetic keypad allowing operator
interface w/o opening the enclosure. Touch key access requires
opening the enclosure.
Alarm 1 LED
LCD readout contrast
adjustment
UP
DOWN
NEXT
EDIT
RESET
LED Indicators
Piezo
Alarm 2 LED
Alarm 3 LED
Common Alarm
Level LEDs
KEYPAD
CAL IN PROGRESS
FAULT ALARM
Figure 1-2. Front Panel Display (open enclosure)