HA40 Technical Manual
1-4
The  basic  HA40  consumes  only  1.5  watts  of  10-30 VDC  from  the 
integral power supply.
Optional features, and external devices such as remote transmitters, 
increase power consumption as described below:
Discrete Relay PCB option; add 1.5 watt.
• 
4-20mA Output PCB option; add .5 watt.
• 
TB3 terminals 1 & 2 on the motherboard provide a maximum 
• 
of  350mA  output  power  for  powering  of  auxiliary  external 
devices such as relays, lamps or transmitters (see 
Figure 3-1
). 
Power consumed from these terminals must be included when 
calculating system power consumption.10-0221-4, Analog Input 
PCB option; add wattage for each monitor connected to this 
board’s 24 VDC terminals.
Some applications require HA 40 controllers to source power for high 
power monitors. If the integral 15 watt power in not enough, a 24VDC, 
50 watt power supply, UL rated for Div 2 hazardous areas is available.  
This option is also available  with a Div 1 enclosure if an explosion-
proof enclosure is required. (See 
Section 5 - Specifications
.)
 Warning
A backup, or external DC power source DOES NOT source auxiliary 
power output (see figure 3.1 TB3).
1�3�2 Relays
Two mechanical (dry contact) Common Form C relays are standard and 
may be mapped to various alarm events as described in 
Section 2.3.1
HA40’s may also be equipped with optional solid-state common Form 
A relays (see 
Section 5 - Specifications
 for details) in applications 
requiring non-arcing switching. Solid-state relays are recommended 
for switching of highly inductive loads.
A  six  mechanical  (dry  contact)  Discrete  Relay  option  board  (see 
Section 3.1.6
) provides dedicated Form C relays for ALARM 1, ALARM 
2 and FAULT for all channels.
 Warning
All mechanical (dry contact) relays are rated at 5 Amp for 28 VDC 
and 250 ~VAC RESISTIVE loads. IMPORTANT: Appropriate diode (DC 
loads) or MOV (AC loads) snubber devices must be installed with 
inductive loads to prevent RFI noise spikes.
Optional solid state relays are rated at 2 Amp 12-280~VAC (600Vpk).
Relay wiring should be kept separate from low level signal wiring.
1�3�3 Ambient Temperature Range 
-25 to 50 degrees C
1�3�4 Humidity Range
0 to 90% R. H. Non-Condensing.
1�3�5 Altitude
Recommended up to 2000 meters