5808W3 Photoelectronic Smoke/Temperature 
Detector with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
 
General Information  
Before installing detectors, please thoroughly read these 
installation instructions and Manual A05-1003-002, Guide for 
Proper Use of System Smoke Detectors, which provides detailed 
information on detector spacing, placement, zoning, wiring, and 
special applications. Copies of this manual are available from 
Honeywell. 
NOTICE: This manual should be left with the owner/user of this 
equipment. 
IMPORTANT: This detector must be tested and maintained 
regularly following NFPA 72 requirements. The detector should be 
cleaned at least once a year. 
General Description 
The 5808W3 photoelectronic smoke/heat detector with built-in 
wireless transmitter is intended for use with wireless alarm 
systems that support 5800 series devices. Refer to 
control/communicator installation instructions for compatibility. 
The 5808W3 smoke/heat detector can be used with any 5800 series 
wireless receiver/transceiver for residential installations. For 
commercial installations, the 5881ENHC or the 5883H receiver is 
required. The transmitter can send alarm, tamper, maintenance 
(when control panels are equipped to process maintenance signals), 
and battery condition messages to the system’s receiver. The 
maintenance signal fully complies with the sensitivity test 
requirement specified in NFPA 72, 7-2.2 and is approved by UL. 
Refer to the wireless system’s instructions for the maximum 
number of transmitters that can be supported. 
The 5808W3 incorporates a state-of-the-art optical sensing chamber 
and an advanced microprocessor. The microprocessor allows the 
detector to automatically maintain proper operation at factory 
calibrated detection levels, even when sensitivity is altered due to 
the presence of contaminants settling into the unit’s smoke 
chamber. In order for this feature to work properly, the chamber 
must never be opened while power is applied to the smoke detector. 
This includes cleaning, maintenance or screen replacement. All 
models also feature a restorable, built-in, fixed temperature (135°F) 
thermal detector and is also capable of sensing a pre-freeze 
condition if the temperature is below 41°F. 
The 5808W3 contains a piezoelectric horn which generates the 
ANSI S3.41 temporal pattern in an alarm condition. In alarm, a 
message is also sent to the wireless control panel and the smoke 
detector’s zone number is displayed at the console. The alarm 
message is transmitted every 4 seconds until the smoke or heat 
condition has cleared and the detector has reset. During an alarm 
condition, pressing the detector’s test switch will silence the 
piezoelectric horn for 5 minutes. Once the detector has reset, a 
RESTORE message is transmitted to the control panel and the 
transmitter’s zone number can be cleared from the panel. The built-
in Drift Compensation algorithm automatically maintains the 
sensitivity of the detector. Once the detector reaches its limit of 
compensation, it transmits a maintenance signal to the panel. The 
mounting base installation is simplified by the incorporation of 
features compatible with drywall fasteners or other methods that 
provide a method for securing the detector in place. 
Two LEDs and a sounder on the detector provide local visual and 
audible indication of the detector’s status: 
 
Table 1: Detector LED Modes 
 
Green LED  Red LED 
Piezoelectric 
Horn 
Power-up 
Blinks every 
5 sec 
Blinks every 
5 sec 
Off 
Normal (standby)  Blinks every 
10 sec 
Off Off 
Out of sensitivity 
Off 
Blinks every 
5 sec 
Off 
Freeze Trouble 
Off 
Blinks every 
10 sec 
Off 
Smoke Alarm 
Off 
Blinks every 
1 sec 
Temporal Pattern 
Thermal Alarm 
Off 
Blinks every 
4 sec 
Temporal Pattern 
Low Battery 
Off 
Blinks every 
45 sec 
Chirp every 45 sec 
after LED blinks for 
7 days 
During initial power-up, the red and green LEDs will blink 
synchronously once every 5 seconds. It will take approximately 20 
seconds for the detector to finish the power-up cycle (see Table 1). 
After power-up has completed and the detector is functioning 
normally within its listed sensitivity range, the green LED blinks 
once every 10 seconds. If the detector is in need of maintenance 
because its sensitivity has shifted outside the listed limits, the red 
LED blinks once every 5 seconds. When alarm has been activated 
by smoke, the red LED blinks every 1 second. During a thermal 
alarm condition (>135°F) the red LED blinks once every 4 seconds. 
The LED indication must not be used in place of the tests specified 
under Testing. In a freeze trouble condition, the red LED will blink 
once every 10 seconds (refer to Table 1). If the detector senses a low 
battery condition, the red LED blinks once every 45 seconds. 
To measure the detector’s sensitivity, the i3 Series Model SENS-
RDR Infrared Sensitivity Reader tool (see Figure 4) should be used. 
Refer to instruction manual D100-98-00 for proper use of the SENS-
RDR. 
Low Battery Detection
 
The 5808W3 is powered by a single 3-volt CR123A or DL123A 
Lithium battery (included). The detector checks for a low battery at 
least every 65 minutes. If a low battery is detected, the transmitter 
sends a low battery message to the control panel, which beeps and 
displays the detector’s zone number. In addition, the red LED of the 
5808W3 will blink every 45 seconds and the test switch will be 
disabled. This condition will exist for a minimum of 7 days, and 
then the detector’s horn will “chirp” about every 45 seconds. 
Pressing the test switch during this time will silence the chirps for 
12 hours. The battery should be replaced BEFORE the chirps begin. 
Be sure to replace the battery with a fresh one. 