Maintenance 
NOTE: Before performing maintenance on the detector, notify the 
proper authorities and the central station that maintenance is 
being performed and the system will be temporarily out of service. 
Disable the zone or system undergoing maintenance to prevent any 
unwanted alarms. Power must be removed from the detector before 
performing maintenance of any kind by removing the detector’s 
battery. 
1. 
To ensure proper power-down sequence, battery must be 
removed from detector for a minimum of 20 seconds before 
removing chamber top. 
2. 
Remove the detector cover by turning counterclockwise.  
3. 
Vacuum the cover or use canned air to remove any dust or 
debris. 
4. 
Remove the top half of the screen/sensing chamber by lifting 
straight up (Figure 5). 
5. 
Vacuum or use canned air to remove any dust or particles that 
are present on all chamber sections. 
6. 
Replace the top half of the screen/sensing chamber by aligning 
the arrow on the screen/sensing chamber with the arrow on 
the housing. Press down firmly until the screen/sensing 
chamber is fully seated.  
7. 
Replace the detector cover by placing it over the screen/sensing 
chamber and turning it clockwise until it snaps into place. 
8. 
Reinstall the battery into the battery compartment noting 
proper orientation. 
9. 
Reinstall the detector and test. (See the Testing section.) 
10.  Notify the central station when the system is back in service. 
 
REMOVABLE
DETECTOR
COVER
SCREEN/SENSING
CHAMBER
(TOP HALF)
DETECTOR
HOUSING
 
Figure 5. Removing Screen/Sensing Chamber 
 
 
Specifications  
Power Source: 
One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Sanyo 
CR123A, Panasonic CR123A or ADEMCO 466.) 
Height: 
2.3 inches (58 mm) 
Diameter: 
5.3 inches (135 mm) with mounting base 
Weight: 
8.5 oz. (241 g) without battery 
Operating Ambient Temperature Range: 
32° to 100°F (0° to 38°C)   
Operating Humidity Range: 
0% to 95% Relative Humidity 
Heat Sensor: 
135° F Fixed Temperature Electronic Thermistors  
Freeze Warning Sensor: 
41°F (5°C) 
Agency Listings: 
UL 268 – Commercial and Residential Installations 
 
Please refer to insert for the Limitations of Fire Alarm Systems. 
 
FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE 
INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED. 
 
 
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada.  Operation is subject to the following two conditions:  (1) This 
device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause 
undesired operation. 
 