IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide
 
 
– 8 – 
IPGSM-DP Trouble Detection Information 
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the 
IPGSM-DP to report faults to the Fire Panel.  If Telco 1 is not operational, the Fire Panel will use Telco 2 to 
report events if there are no faults in the iGSM Communications module.  
Fault Condition 
Indication to Fire Panel 
PowerBoost1 fault 
Telco 2 is cut.  
iGSM Communications Module fault 
 
  Failure of one of the two 
communications paths. 
Telco 2 is cut. 
  Failure of both communications 
paths. 
Telco 1 and 2 are cut. 
Dialer Capture Module buffer is full. 
Hang up.  (Panel will retry, giving the buffer a chance to empty.)  
 
Dialer Capture Module Information 
 
LED Indicator 
STATUS 
RED – Steady ON 
Messages exist in buffer. 
RED – Flashing 
No messages to be sent.  Waiting for messages. 
GREEN – Steady ON 
Normal Indication. 
GREEN – Blinks every 2 sec. 
PowerBoost1 communication problem. 
GREEN – Blinks twice every sec. 
Communication Module connection is lost. 
GREEN – Blinks 10 times every sec. 
PowerBoost1 and Communications Module connection is lost. 
 
iPGSM-COM-004-V0
Dialer Capture Module
Telco 1
Telco 2
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
PWR
GND
Tip 1
Ring 1
Data Out
Data In
12V  In
GND
RED
GREEN
 
LED Display Information 
 
Panel Status 
LED Indicator 
RADIO TROUBLE 
Yellow – ON when radio trouble is present. 
 
Buzzer – Upon loss of AC power, this will 
beep once every 10 seconds.  
LOW BATTERY 
Yellow – ON when battery is low. 
 
Yellow – (not used)   
AC LOSS 
Yellow – ON when no AC is present.   
AC ON 
Green – ON when AC is present. 
 
Note: Telco ports 1 (primary dialer) 
and 2 (secondary dialer) may be 
used instead of the terminal board. 
Whichever connection method is 
used, both Telco paths must be 
connected to the Fire Panel.  
iPGSM-COM-006-V0
Buzzer