IPGSM-DP Trouble Detection Information
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the
IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to
IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to
report events if there are no faults in the iGSM Communications module.
Fault Condition
Indication to Fire Panel
PowerBoost1 fault
Telco 2 is cut.
iGSM Communications Module fault
Failure of one of the two
communications paths.
Telco 2 is cut.
Failure of both communications
paths.
Telco 1 and 2 are cut.
Dialer Capture Module buffer is full.
Hang up. (Panel will retry, giving the buffer a chance to empty.)
Dialer Capture Module Information
LED Indicator
STATUS
RED – Steady ON
Messages exist in buffer.
RED – Flashing
No messages to be sent. Waiting for messages.
GREEN – Steady ON
Normal Indication.
GREEN – Blinks every 2 sec.
PowerBoost1 communication problem.
GREEN – Blinks twice every sec.
Communication Module connection is lost.
GREEN – Blinks 10 times every sec.
PowerBoost1 and Communications Module connection is lost.
iPGSM-COM-004-V0
Dialer Capture Module
Telco 1
Telco 2
ECP
Tip 2
Ring 2
ZN-
EOL
EOL
ZN+
PWR
GND
Tip 1
Ring 1
Data Out
Data In
12V In
GND
RED
GREEN
LED Display Information
Panel Status
LED Indicator
RADIO TROUBLE
Yellow – ON when radio trouble is present.
Buzzer – Upon loss of AC power, this will
beep once every 10 seconds.
beep once every 10 seconds.
LOW BATTERY
Yellow – ON when battery is low.
Yellow – (not used)
AC LOSS
Yellow – ON when no AC is present.
AC ON
Green – ON when AC is present.
Note: Telco ports 1 (primary dialer)
and 2 (secondary dialer) may be
used instead of the terminal board.
Whichever connection method is
used instead of the terminal board.
Whichever connection method is
used, both Telco paths must be
connected to the Fire Panel.
iPGSM-COM-006-V0
Buzzer