Honeywell IPGSM-DP Manual Do Utilizador

Página de 16
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide 
 
– 9 – 
 
Note: If a wire pulled out of the LED Board Connector  
refer to the diagram on right and reinsert wire, ensuring  
the connector pin is locked in. 
 
 
 
PowerBoost1 Module Information 
 
LED Indicator 
STATUS 
AC  
(green) 
AC power available. 
ACTIVE  
(green) 
Cyclical flashing – normal communications. 
Repetition of 3 flashes – loss of communications. 
LOW BATT (yellow) 
Missing or low battery. 
TROUBLE (yellow) 
One or more trouble conditions exist, such as; overload, output supervision, 
ground fault, or charger failure. 
 
Notes:  
 
If AC power is lost and the battery voltage falls below 10v, the module's output voltage will be 
turned off.  The output power is turned back on when AC power is restored. 
 
You must use the DIP switch settings shown below. 
 
iPGSM-COM-003-V0
TROUBLE LED
INDICATOR
PowerBoost1
1
5
ON
2 3 4
Confiure DIP switch
as shown:
AC LED
INDICATOR
ACTIVE LED
INDICATOR
LOW BATT LED
INDICATOR
1
5
ON
2 3 4
(Switch handle = white)
 
NC
NC
LED Board 
Connector
Wires
Violet
Black
White
Red
Brown
Yellow
Gray