Lochinvar SNR150-100 Manual Do Utilizador

Página de 76
64
12  
Troubleshooting 
Table 12B - Inlet/Outlet Tank Sensor Resistance vs. Temperature
Temperature °F
Resistance 
Temperature °F
Resistance 
50
18,780
158
1,990
68
12,263
176
1,458
86
8,194
194
1,084
104
5,592
212
817
122
3,893
--
--
140
2,760
--
--
Table 12C - Flue Temperature Sensor Resistance vs. Temperature
Temperature °F
Resistance 
Temperature °F
Resistance 
68
14,773
176
1,707
86
9,804
194
1,266
104
6,652
212
952
122
4,607
230
726
140
3,252
248
560
158
2,337
--
--
Checking temperature sensors
The water heater temperature sensors (inlet water, outlet water, tank water, and flue) are all resistance type devices. The following 
tables show the correct values for the sensors at various temperatures.  Use an ohmmeter to read the resistance of the sensor at a 
known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.
       
Installation & Service Manual
TM