Lochinvar 000 BTU/HR Manual Do Utilizador

Página de 52
On boilers, the pump will operate whenever the
“W” terminal is energized.
B. Location - The appliance should be located
within a room having a temperature safely
above freezing [32°F(0°C)].
C. Shutdown and Draining - If, for any rea son,
the appliance is shut off, the following
pre cau tion ary measures must be taken:
1.  Shut off gas supply,
2.  Shut off water supply.
3.  Shut off electrical supply.
4. Drain the heat exchanger completely. Re 
-
move one 3/8" NPT plug or bulb well from the
inlet side and one from the outlet side of the
front head er of the heat exchanger.  
5.  Drain the pump.  Remove the 3/4" plug in
the bypass loop.
1.
Inspect the burners to be sure they are prop er ly
aligned.
2.
Inspect the pilot gas line, thermocouple leads,
ignition leads and wire connections to the gas
valve to be sure none were damaged during
shipment.
3.
Check to ensure that gas connections have been
made properly and the gas line is purged of air.
4.
Check to ensure that water connections are tight
and the appliance and piping system have been
properly filled.
5.
Ensure that discharge from the relief valve has
been piped to a floor drain.
6.
Verify that properly sized combustion and
ven 
ti 
la 
tion air openings are provided and not
obstructed in any way.
7.
Check carefully for gas leaks.
8.
Read the appliance’s safety warnings, light 
ing
instructions and check out procedure carefully, 
be fore firing the system.
A. This appliance has a pilot which must be
ig 
nit 
ed by hand.  When lighting the pilot,
follow these instructions exactly.
B.  BEFORE OPERATING, smell around the
appliance area for gas.  Be sure to smell next to
the floor because some gas is heavier than air
and will settle to the floor.
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neigh bor’s phone.  Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fire department.
C.  Use only your hand to push in or turn the gas
control knob.  Never use tools.  If the knob will
not turn by hand, don’t try to repair it, call a
qualified ser vice technician. Force or attempted
repair may result in a fire or explosion.
D.  Do not use this appliance if any part has been
under water.  Immediately call a qualified
service technician to inspect the appliance.  The
pos si ble damage to a flooded appliance can be
extensive and present numerous safety hazards.
Any appliance that has been under water must
be replaced.
1.
STOP! Read the safety information.
2.
Remove the control panel door.
24
PRE-START CHECKLIST
LIGHTING INSTRUCTIONS FOR
STANDING PILOT MODELS (F1)
MODELS 90,000 THRU 270,000 Btu/hr
INPUT FOR YOUR SAFETY READ
BEFORE OPERATING
If you do not follow these in struc tions exactly, a
fire or explosion may result causing prop 
er 
ty
damage, personal injury or loss of life.
 WARNING
WHAT TO DO IF YOU SMELL GAS
LIGHTING INSTRUCTIONS