Circuit Breaker and Wire Sizing
The minimum circuit breaker size and maximum allowable wire lengths for 
connection of motor to the SubDrive300 are given in the following table:
A 10-foot section of cable is provided with the SubDrive300 to connect 
the pressure sensors.
NOTE:
•  Maximum allowable wire lengths are measured between the 
controller and motor.
•  Aluminum wires should not be used with the SubDrive300.
•  Wire sizing between the service entrance and the controller must 
be suffi cient to provide the required maximum input amps to the 
controller while conforming to local standards and codes.
•  SubDrive300 minimum breaker amps may be lower than AIM 
Manual specifi cations for the motors listed due to the soft-starting 
characteristic of the SubDrive300 controller.
Controller 
Model
Franklin Electric
Motor Model
HP
Breaker 
Amps
AWG Copper Wire Size
14
  12 
10
8
6
4       
SubDrive300 234  317  xxxx
5
40 
140                 230 370 590 920 1430
Table 2: Minimum Breaker Size and Maximum Cable Length (in Feet)